7 Servicing
RPI(L/H)-(0.4-6.0)FSRE - Ducted indoor unit
SMGB0137 rev.0 - 05/2021
231
7
RPIL-(0.4-1.5)FSRE
1 Remove the motor cover as explained in “7.5.4 Removal of the motor cover”.
2 Remove the screws of the upper side of the fan casing (2 screws per casing, 4 in total)
3 Press the locks and remove half of the fan casing.
4 Remove the bearing stay screws.
5 Remove the motor support screws and carefully remove the motor together with the fan.
6 Loosen the screws securing the fans to the motor shaft with a hexagon wrench and remove the fan runners and the
bearing support plate from the shaft.
7 Loosen the screws from the coupling securing the shaft to the motor shaft with a hexagon wrench and remove the
shaft.
Locks
Coupling
Locks
Motor support screws
Casing screw
Bearing stay screw
Bottom side