7 Servicing
RPK-FSR(H)M - Wall mounted
SMGB0137 rev.0 - 05/2021
245
7
Attaching at panel.
Insert completely the left and right arm shafts of at panel into
the holes along the guide at the front panel. After the at panel is
attached completely, insert the catches for air lter to x it.
Flat panel
Front panel
Hole
Guide at
front panel
For RPK-(2.0-4.0)FSRM
1 Remove the air lter according to the “7.7.1 Removal of the air lter” chapter.
2 Hold both sides of at panel and open it fully. After the right arm shaft is pushed inward and shafts are removed from
the front panel, pull the at panel forward while the right arm shaft is slightly pushed inward.
3 Remove 3 bushes and then 3 screws. Pull the center of the bottom side in the at panel (2 positions) and the lower
side of the louver (2 positions) forward to release the catches. Use a slotted screwdriver when the catches are dicult
to release.
4 Remove the front panel carefully so that it does not touch the horizontal louver attached to the air outlet. Slightly lift
the front panel up to release the catches (4 positions) on the upper side of the unit. Then pull the front panel forward
to remove it.
! CAUTION
Take special care not to be injured by the heat exchanger ns.
? NOTE
When releasing the catches, snap sound is heard. This is the sound made when the catches are released and so there are no safety
concerns.
Flat panel
Push the shaft
toward arrow
direction
Remove this part
from the hole
Bush (3 pieces)
Screw (3 pieces)