EasyManuals Logo

Hitachi RCUE100AG2 User Manual

Hitachi RCUE100AG2
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
SMGB0003 rev.0-01/2007
page 16
Product range and
specifications
1.2. General data for RHUE40~240AG2
MODEL RHUE40AG2 RHUE50AG2 RHUE60AG2 RHUE70AG2
Cooling Capacity
kW
106
123
148
169
Heating Capacity
kW
110
127
152
185
Total Power input in cooling
kW
36.4
42.7
52.3
59.8
Total Power input in heating
kW
40.7
44.5
54.3
67.7
Outer Dimension
Height
Height
mm
2.430
2.430
2.430
2.430
Width
mm
1.900
1.900
1.900
1.900
Depth
Depth
mm
1.900
1.900
1.900
2.500
Cabinet colour
-
Natural Grey
Net weight
Kg
1.550
1.600
1.670
1.880
Compressor type
-
Semi-Hermetic screw type
Models
-
40ASC-Z
40ASC-Z
50ASC-Z
60ASC-Z
Quantity
-
1
1
1
1
Oil heater
W
150
Capacity control
-
Continuous Capacity Control
Continuous Capacity Control
Continuous Capacity Control
%
15~100
Water side heat exchanger
-
Brazing plate type
Air side heat exchanger
-
Multi-Pass cross fi nned tube
Fan Motor (pole)
kW
0.38 (8)
Quantity
-
4
4
4
6
Refrigerant type
-
R407C (Factory charged)
Flow control
-
Electronic expansion valve
Number of independent circuits
-
1
1
1
1
Quantity of refrigerant
-
39
46
41
48
Oil type
-
JAPAN ENERGY FREOL UX300 (Ester)
Water pipe connection
Inch
3” Victaulic (1xInlet/1xOutlet)
Control system
-
Micro-processor control
Chilled water outlet temperature
ºC
-10 (Option) 5~15
Heated water outlet temperature
ºC
35~55
Condenser air inlet temperature
ºC
-15~46 for cooling operation
Evaporator air inlet temperature
ºC
DB: -9.5~21/ WB:-10~15.5 for heating operation
Permissible water pressure max.
Permissible water pressure max.
Permissible water pressure max.
MPa
1.0
Safety and protection devices
-
Reverse Phase Protection, Fuse and Thermal Relay for Compressor,
Reverse Phase Protection, Fuse and Thermal Relay for Compressor,
Reverse Phase Protection, Fuse and Thermal Relay for Compressor,
Reverse Phase Protection, Fuse and Thermal Relay for Compressor,
Reverse Phase Protection, Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Fuse and Internal Thermostat for Fan Motor, Control Circuit Fuse,
High Pressure Switch, Low Pressure Control,
High Pressure Relief Valve, Discharge Gas Temperature Control,
Suction Gas Temperature Control, Freeze Protection Control
and Compressor Operation Hour Meter
and Compressor Operation Hour Meter
and Compressor Operation Hour Meter
Power suply
Power suply
-
3~, N/380-415V/50Hz
NOTES:
(1) The nominal cooling capacities are based on the European Standard EN12055.
Chilled Water Inlet / Outlet Temperature : 12/7 ºC
Condenser Inlet Air Temperature : 35 ºC
(2) The nominal heating capacities are based on the European Standard EN12055.
Heated Water Inlet / Outlet Temperature : 40/45 ºC
Evaporator Inlet Air Temperature : 6 ºC (WB)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RCUE100AG2 and is the answer not in the manual?

Hitachi RCUE100AG2 Specifications

General IconGeneral
BrandHitachi
ModelRCUE100AG2
CategoryChiller
LanguageEnglish

Related product manuals