6.5. Check items in daily operation
6.5. Check items in daily operation
6.5. Check items in daily operation
Check items Check contents Result (write the value or
X
)
Check of around of chiller unit
Pressure, quantity and quality of chilled (heating)
Check them while pouring water
Pipe of chilled (heating) water
Check of screws and bolts etc
Re-tighten those which are loosed
Re-tightening of electrical wiring terminal
Confi rm it while pouring water
Dirtiness of air side heat exchanger
Clean it by pouring hot (40°C) water.
Confi rm it while pouring water
Cleaning of inside/outside of machine room
Check valves, fl are parts,
Water side heat exchanger
4 way valve (only cooled heat pump)
High pressure block switch
Cleaning of inside/outside of unit
Interphase voltage of compressor
Check compressor, fan, pipe etc.
Operation adjustment and automatic operation
Check the activation of ON, OFF,
High pressure block switch
Check the activation value and setting
Check the activation value and setting
4 way valve (only cooled heat pump)
Check the state of switch from cooling
Check the state of switch from cooling
to heating and vice versa.
Instruction on operation method
Inlet temperature of chilled (heating) water
Outlet temperature of chilled (heating) water
Inlet DB(WB) temperature of air side heat
Water fl ow of water side heat exchanger
6.6. Caution on handling of R407C
6.6. Caution on handling of R407C
6.6. Caution on handling of R407C
The refrigerant is HFC type refrigerant whose ozone destruction coeffi cient is ZERO. If other refrigerant is
mixed, the property of refrigerant is changed and may cause a problem. The following points should be taken
into account on its handling.
Refrigerant should be added in liquid state not in gas state. R407C is nonazeotropic refrigerant mixture,
and compositions of boiling point are different. Therefore, if it is added in gas state, refrigerant, easy to
evaporate, is added and refrigerant, hard to evaporate, remains in a refrigerant tank.
Confi rm if the tanks specialised for R407C.
The tank should be set so that refrigerant can be added in gas state.
The valves or hose for charge should be specialised for R407C.