4 Electrical and control settings
Unit electrical wiring and connection
SMGB0099 rev.0 - 12/2016
154
4.1.13 DX-Interface electrical wiring
Connect the electrical wires between the indoor unit and the outdoor unit, as shown in the next diagram.
Follow the local codes and regulations when performing the electrical wiring.
Use shielded wires for intermediate wiring to protect the units from noise obstacle at length of less than 300 m and
size in compliance with local codes.
In the event that a conduit tube for eld-wiring is not used, x rubber bushes to the panel with adhesive.
All the eld wiring and equipment must comply with local and international codes.
When a cable gland is not used, it must be sealed properly in order to ensure the correct control box sealing.
! CAUTION
Pay attention to the connection of the operating line. Incorrect connection may cause PCB failure.
? NOTE
Packing gland diameter specication: 6.0 mm (min) to 12.0 mm (max). If needed, install additional tube insulation or wind with insulation
tape around the wire to make the wire thicker.
Control box terminal board
DX-Interface EXV-(2.0-10.0)E2
Terminal board 1
Terminal board 2
(*)
? NOTE
(*) Packing gland for thermistor installation.