2 Unit installation
RCI - 4-way cassette
SMGB0099 rev.0 - 12/2016
20
2.1.2  Unit installation
 
Initial checks
Install the indoor unit with a proper clearance around it paying careful attention of installation direction for the piping, 
wiring and maintenance working space, as shown below.
Provide a service access door near the unit piping connection area on the ceiling.
Service 
Access Door
Service Access 
Door
Piping 
Connection
Drain Piping 
Connection
Check space between ceiling and false ceiling is enough as indicated below.
Check the ceiling surface is at for the air panel installation work.
Clearance: 10-20mm
Unit High 
In False Ceiling
Unit HP A(mm)
RCI-1.0 to 2.5HP 238
RCI-3.0 to 6.0HP 238
 
Opening of false ceiling
Cut out the area for the indoor unit in the false ceiling and install suspension bolts, as shown below:
20 20
840
760
2020
760
4-12 x32
Dimension of opening 860 to 910
(Unit size)
(Dimension of 
suspension bolts)
Holes (for 
suspension bolt)
(Dimension of suspension 
bolts)
840 (Unit size)
Dimension of opening 860 to 910
Piping connection 
side
Drain piping 
connection side
4-Positions of suspension 
bolts (M10 or W3/8) 
(Field-supplied)
 
Check to ensure that the ceiling is horizontally level, otherwise water can not ow.
Strengthen the opening parts of the false ceiling.