6 Optional functions
Complementary systems
SMGB0099 rev.0 - 12/2016
228
Where Code Function DX KPI-E4E KPI-X4E Setting Status Remarks
RCS 
setting
E4
Precooling /  
Preheating period
- O O
00: 0 minutes 
01: 30 minutes 
02: 60 minutes
The unit starting is 
delayed a certain time 
while A/C system starts 
working.
E5
High ventilation after 
switch ON
O O O
00: 0 minutes 
01: 60 minutes
PCB1 
& RCS
i1 
CN3 1#-2# input 
(*1)(*2)
O O O
00:No setting 
01:Room Thermo (Cooling) 
02:Room Thermo (Heat)  
03:Remote ON/OFF 1 (Contact)  
04: Remote ON/OFF 2 (Pulse) 
05:Remote ON/OFF2 (Stoppage/
Pulse) 
06:Forced Stop 
07: Remote H/C changeover
When Thermo ON/OFF 
input enabled (PCB2-
DSW16=ON), i1 optional 
signal is not available
i2 CN3 2#-3# input O O O
o1 CN7 1#-2# output O O O
00:No setting 
01:Run 
02:Alarm 
03:Cooling 
04:Thermo ON 
05:Heating 
06:Defrost
o2 CN7 1#-3# output O O O
o3 CN8 1#-2# output O O O
PCB1 
(PSW)
Ct
CO2 sensor type  O O O
00: ON/OFF CO2 signal 
01: Activated 4-20mA signal 
02: Activated 0-10V signal
S1: Set minimum O O O
Default (00: 4 / 01: 0) 
Range (00:4~S2 / 01: 0~S2)
S2: Set maximum O O O
Default (00: 20 / 01: 10) 
Range (00: S1~20 / 01: S1~10)
dF Defrost Fan  O - O
00: Fan Low operation (Default) 
01: Fan kept operation 
02: Fan stopped operation
? NOTE
•  (*1): CO2 sensor signal must be an ON/OFF signal. CO2 sensor must be connected to CN3, pins 1-2, for i1 input signal (refer to 
outdoor unit technical catalogue for further information about the connection specs).
•  (*2): When using this option i1 standard functions become deactivated i2 input signal is not affected.
6.3.1.1  DX-Interface
Main optional functions on DX-Interface series 2
Optional function Explanation
EC Fan or Tap Fan The control of tap fans and EC fans is possible from the DX-Interface series 2.
Defrost signal Output signal get from the DX-Kit when the system is in defrost mode.
Fan operation during defrost
During defrost operation three different fan speed settings are possible: fan speed 
kept as set, fan speed reduced to low speed and fan stoppage.
Thermo-on / thermo-off by an external input Instead of typical control logic.
Operation delay
Once the system is turned on, the unit is kept in off during an specic time. Useful 
for applications where the DX-Kit is focused in comfort and not room conditioning
Thermistor selection
Option to select between inlet thermistor, external thermistor or remote controller 
thermistor to perform the cycle control (as inlet temperature) (Only if demand control 
is based on inlet temperature).
Fan Stoppage delay
Once the system is switched off, the unit keeps running for a suitable period of time, 
to for example, perform the air renovation once the activity is conclude.
CO2 sensor
By the action of an ON/OFF CO2 sensor, the DX-Kit switches the fan speed to high 
while the CO2 concentration exceeds the sensor detection threshold.