9 Servicing
RPC-(3.0-6.0)FSN3E - Ceiling type
SMGB0099 rev.0 - 12/2016
277
9
9.4.4 Removal of the fan motor
1 Open the air inlet grille as indicated in chapter “9.4.1
Removal of the air lter”.
2 Remove the air inlet clip.
Air inlet
panel
Stay
Fixing screw
3 Separate the indoor fan motor connector.
Wiring panel
Part
1 Electrical box
4 Remove the screws securing the box and attach to the
lower frame.
! CAUTION
Hold onto the electrical box to prevent it from falling.
5 Press the four attachment points of the cover (1) inwards
and remove it.
Hook
Casing
6 Loosen the coupling screws using a wrench.
7 Remove the securing ange and remove the fan motor 
by sliding it backwards.
! CAUTION
Hold onto the motor to prevent it from falling.
Motor
To
loosen
Allen key
Fixing screw
Fixing band
Coupling