Electrical Wiring
l
 
Wrap the accessory packing around the 
wires, and plug the wiring connection hole 
with the seal material to protect the product 
from any condensate water or insects.
l
 
Tightly secure the wires with the cord clamp 
inside the indoor unit.
l
 
Lead the wires through the knockout hole in 
the side cover when using conduit.
l
 
Secure the cable of the remote control switch 
using the cord clamp inside the electrical 
box.
7.1  General Check
(1)  Make sure that the eld-selected electrical 
components (main power switches, circuit 
breakers, wires, conduit connectors and 
wire terminals) have been properly selected 
according to the electrical data given in 
“Technical Catalog”.  Make sure that the 
components comply with National Electrical 
Code (NEC).
(2)  Use the shielded twist pair cable for the 
control cable between the outdoor unit and 
the indoor unit, the control cable between 
indoor units and the remote control switch 
cable of PC-ARF.
(3)  Check to ensure that the power supply 
voltage is within ±10% of the rated voltage.
(4)  Check the capacity of the electrical wires. 
If the power source capacity is too low, the 
system cannot be started due to the voltage 
drop.
(5)  Check to ensure that the earth wire is 
connected.
The procedure of the wiring work shall be 
performed according to this manual and “Installation 
& Maintenance Manual” of the outdoor unit.
l
The electrical wiring work must be performed 
by authorized installers.  If not, it may cause 
an electric shock or a re.
l
Perform the electrical work according to 
each regulation of region and “Installation 
& Maintenance Manual”, and the dedicated 
electrical circuit must be used.  If not 
performing the electrical wiring work 
completely or a capacity shortage of the 
power circuit, it will cause an electric shock 
or a re.
l
Use the specied cables for wiring between 
the outdoor unit and indoor units.  Selecting 
incorrect cables will cause an electric shock 
or a re.
l
Install an ELB (Earth Leakage Breaker) in the 
power source.  If not used, it will cause an 
electric shock or a re.
l
Turn OFF the main power switch of the 
indoor unit and the outdoor unit before an 
electrical wiring work or a periodical check 
is performed.  If not, it will cause an electric 
shock or a re.
l
Check to ensure that the indoor fan and the 
outdoor fan have stopped before electrical 
wiring work or a periodical check is 
performed.
l
Protect the wires, drain pipe, electrical parts, 
etc. from rats or other small animals. 
If not protected, rats may gnaw at unprotected 
parts and at the worst, a re will occur.
l
Tighten screws according to the following 
torque.
  M3.5: 1.2 N-m 
  M4:  1.0 to 1.3 N-m
l
Connect earth wires for the outdoor / indoor 
unit to prevent an electrical shock or an 
unexpected accident.  The earth resistance 
must be less than 1 megohm.   The earth work 
must be performed by authorized installers.
l
 Turn completely OFF the power source to 
prevent an electrical shock when opening the 
service cover to perform the electrical work 
or the maintenance.
l
 Pay attention not to bite electrical wirings 
when attaching the service cover. It may 
cause an electrical shock or re.