P5416543 
39
(4)  Capacity Code Setting (DSW3) 
No setting is required, due to setting 
before shipment.  This switch is utilized 
for setting the capacity code which 
corresponds to the Horse Power of the 
indoor unit.
(5)  Unit Model Code Setting (DSW4) 
No setting is required. 
It is for setting the model code 
of the indoor unit.
(6)  Refrigerant Cycle No. Setting 
(RSW2 & DSW5) 
Setting is required.  Setting positions 
before shipment are all OFF.
(7)  Fuse Recover (DSW7)
  *  Factory Setting
  *  In the case of applying high 
  voltage to the terminal 1 and  
  2 of TB2, the fuse (0.5A) on 
  the PCB is cut. 
  In such a case, rstly 
  reconnect the wirings    
  correctly to TB2, and then 
  turn on No.1 pin.
7.7  Function Selection  
by Remote Control Switch
Each function can be selected from the remote 
control switch (PC-ARF).
The detail should be referred to “Installation & 
Maintenance Manual” for the remote control switch 
and “Technical Catalog”.
l
Circulator Function at Heating Thermo-OFF 
This function maintains the fan operation by the 
set air ow volume at the heating Termo-OFF. 
It is for improvement of temperature distribution 
at high height ceiling site.
(8)  Optional Function Setting (DSW9) 
No setting is required. 
Setting positions before 
shipment are all OFF.
Turn OFF all the power supply of the indoor unit 
and the outdoor unit before Dip Switch setting. 
If not, the setting is invalid.
Setting
Position
2.0 2.5Horsepower
Setting
Position
3.0
4.0 5.0 6.0Horsepower
1.5
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
3
4
1
0
8
9
2
5
6
7
3
4
1
0
8
9
2
5
6
7
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5 (Tens Digit)
Refrigerant Cycle No. Setting
RSW2 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.5 Cycle
DSW5
RSW2
Set All Pins OFF
Set at "5"
Before shipment, DSW5 and RSW2 are set at "0".
(a) for Units Supporting H-LINK II
     The ref. cycle Nos. can be set for Max. 64 cycles.
     (No. 0~63)
(b) for Units Supporting H-LINK
     The ref. cycle Nos. can be set for Max. 16 cycles.
     (No. 0~15)
1234
NOTE
l
 
The “
n
” mark indicates position of dip switches. 
Figures show setting before shipment.
l
 
When the unit number and the refrigerant cycle 
are set, record the unit number and refrigerant 
cycle to facilitate maintenance and servicing 
activities thereafter.