P5416543
45
9.
Safety and Control Device Setting
Indoor Unit
Model
RPC-1.5FSN3, RPC-2.0FSN3
RPC-2.5FSN3, RPC-3.0FSN3
RPC-4.0FSN3, RPC-5.0FSN3
RPC-6.0FSN3
For Evaporator Fan Motor
Thermostat Cut-Out
o
C 100
+15
-10
Cut-In
o
C 95
+15
-10
For Control Circuit
Fuse
Capacity A 5
Freeze Protection
Thermostat Cut-Out
o
C 0
Cut-In
o
C 11
Thermostat
Differential
o
C 2