2-50
SERVICING
(2.2 In-the-Ceiling Type)
(3) Remove the lower M4 screws (Q’ty: D) fixing the discharge flange.
* Q’ty of Screws (D): 2 (For RPI-0.8 to 1.5FSG1)
3 (For RPI-2.0 to 4.0FSG1)
4 (For RPI-5.0FSG1)
Phillips ScrewdriverTool
TURN OFF all power source switches.
(4) Remove eight (8) M4 screws fixing the lower cover at the indoor heat exchanger side and remove the
lower cover.
(5) Remove M4 screws (eight (8) for each side) fixing the side frames at both sides and remove the side
frames.
(6) Pull the drain pan downward.
Phillips Screwdriver,
Bucket (approx. 5 liters content)
Tool
Discharge Flange
Screws (M4xD)
Screws (M4x8)
(Both Sides)
Side Frame
Drain Pan
Side Frame
Lower Cover
Screws (M4x8)

Table of Contents