4-13
OPTIONAL FUNCTION
(4.2 Indoor Unit)
Factory-Setting
(b) Press the “TIME ” switch or the “TIME ” switch, the indication of port at the segments for timer
setting time indication is changed as shown below.
Select the port for allocating the input and output signal.
When pressing the “TIME ” switch
When pressing the “TIME ” switch
(c) Press the “CHECK” switch, and the code of the input and output signal at the segments for setting
temperature indication is changed as shown below.
Select the input and output signal to be allocated to the port.
(5) Selection of Other Indoor Unit
At the input and output setting mode, press the “TEMP ” switch or the “TEMP ” switch, the
condition of the remote control switch is changed so that the indoor unit can be selected for the input
and output setting described in the item (3).
(6) Return from Input and Output Setting Mode
Press the “RESET” switch, the input and output setting is memorized and the mode is returned to the
normal condition.
4.2.2 Remote Control Thermistor Function
The temperature can be controlled by the built-in thermistor of the remote control switch (remote control
thermistor) instead of the thermistor for the suction air of the indoor unit.
NOTES:
1. Even in case of controlling temperature by the remote control thermistor, the detected temperature by
the thermistor for the suction air of the indoor unit is applied for the activation of the protective devices in
relation with the thermostat for the suction air of the indoor unit.
2. In temperature control by the remote control thermistor, when the detecting temperature is abnormal due
to the failure of the remote control thermistor, etc., the thermistor to be used is changed to the thermistor
for suction air of the indoor unit automatically.
3. In case of using this remote control thermistor function, select the location for installing the remote
control thermistor as follows;
* where the average temperature of the room can be detected.
* where the thermistor is not exposed to the sunlight directly.
* where the heat source is not near the thermistor.
* where the outdoor air do not affect the room temperature by opening and closing the door, etc.
4. In case of using two remote control switches (Main and Sub), this remote control thermistor function is
available only for the main remote control switch.
Refer to the item 4.4.4 “Optional Function Setting” for the setting procedures of optional functions.
5. This function is not available while the remote sensor is utilizing. (Priority of Remote Sensor)
>
>
i1 i2 o1 o2 o3
00 01 02 03 04 05 06 07 08
Connector No. Pin No. of Connector Setting When Shipping Indication 2
Input CN3 #1 - #2 Remote Control ON/OFF Function 1 03
#2 - #3
Cancellation of Commands from Remote
Control Switch after Forced Stoppage
06
Output CN7 #1 - #2 Operation Signal 01
#1 - #3 Alarm Signal 02
CN8 #1 - #2 Thermo-ON Signal during Heating 06