4-12
OPTIONAL FUNCTION
(4.2 Indoor Unit)
(4) Setting Procedures
(a) At the input and output setting mode,
the indication on the remote control switch is
changed as shown in the right figure.
The allocated port for input and output
signal is indicated at the segments for timer
setting time indication.
Refer to the indicated port and
the connector of the indoor PCB for
the table below.
The codes of the input and output signals are indicated at the segments for setting temperature
indication.
Refer to the indicated code and the input and output signal for the table below.
Indications and Input and Output Signals
1
2
Indication 2 Input Output
00 Not Set Not Set
01 Control by Field-Supplied Room Thermostat (Cooling) Operation Signal
02 Control by Field-Supplied Room Thermostat (Heating) Alarm Signal
03 Remote Control ON/OFF Function 1 Cooling Operation Signal
04 Remote Control ON/OFF Function 2 (Operation) Thermo-ON Signal during Cooling
05 Remote Control ON/OFF Function 2 (Stop) Heating Signal
06 Cancellation of Commands from Remote Control
Switch after Forced Stoppage
Thermo-ON Signal during Heating
07 Cooling or Heating Operation Mode Setting Total Heat Exchanger Operation Signal
08 Input for UP/DOWN Grille (Not Available) Output for UP/DOWN Grille
(Not Available)