7-17
7.2.13 Exception response
The inverter returns a response to the request, but
if an error occurs in the request, it is to return an
exception response.
[Exception response]
(Example)
In case configuring nonexistent address to holding
registers using the Modbus function code "03h
(Read holding registers)", it is to return the
exception response shown below.
Hi: high order
Lo: low order
*1) When returning the exception response, being
configured adding "80h" to the function code of
the request.
■Function codes of exception response
In the case, 3 byte lengths
(address 6 through 8).
The function code in the
request: 03h plus 80h