4.4.5 Release terminal
The function release is activated when voltage is removed
from release terminal after voltage is applied to release
terminal and currents flow. Releasing by release signal is
activated when the parameter [1-12]/[2-12] sets to
02:With release signal.
■Related parameter
00:Without release signal /
01:With safety signal /
02:With release signal
00:Without release signal /
01:With safety signal /
02:With release signal
4.4.6 Holding function of STO state
When the parameter [1-12]/[2-12] is set by 01:With safety
signal or 02:With release signal, STO state can be held until
releasing intentionally by safety signals or release signal
after STO state is activated.
When the parameter [1-12]/[2-12] is set by 00:Without
release signal, STO state can be released automatically
after safety inputs are released. In this case, inverter starts
to output the power to the motor automatically after
safety inputs are released when the run command is input
after releasing STO inputs or the run command is kept
before releasing STO input. Considering the above-
mentioned behavior, please apply at least one of the
measures below in order to fulfill the requirement of
EN60204-1:
(1) The RUN command is released simultaneously when
the STO inputs are activated and then given when
restart of the inverter is requested intentionally by an
operator of the system.
(2) The system is designed so that the safety inputs to P1-
FS are released only when restart of the system is
requested intentionally by an operator of the system.
■Related parameter
00:Without release signal /
01:With safety signal /
02:With release signal
00:Without release signal /
01:With safety signal /
02:With release signal