11-2
Specification and Technical data
11.3 Electrical specification
Descriptions and specifications of the terminals are listed
in the table below.
Note: Corresponding to “Digital input type 1” defined in
IEC61131-2
Length of cabling connected to the above terminals other
than ST1, ST2, and STC must be twenty (20) meters or
shorter. Length of cabling connected to ST1, ST2, and STC
must be one (1) meters or shorter.
*1) These are the terminal symbols on the connector.
They are different from the terminal symbols on the
front label.
*2) In case of use of an external power supply, input
voltage range is set from DC18V to 27V.
Electrical
Characteristics
Input terminal 1 for the redundant paths
Input current: 6mA
Input voltage :
DC18V to DC27V *2)
Input terminal 2 for the redundant paths
Input terminal 3 for the redundant paths
24V power supply output terminal for input
terminal
DC24V power supply output terminal for input
terminal
Common for input terminal
Common for input terminal
Release terminal for Safety function.
Short to ST1 terminal on P1
Short to ST2 terminal on P1
Short to STC terminal on P1
Output terminal 11 on path 1
Output terminal 11 for the redundant
paths
Output terminal 11 on path 2
Output terminal 12 on path 1
Output terminal 12 for the redundant
paths
Output terminal 12 on path 2
24V power supply input terminal for output
terminal 11/12 on path 1
Power supply input terminal for output
terminal 11/12 on path 1
Consumption
current:150mA
Input voltage :
DC18V to DC27V *2)
24V power supply input terminal for output
terminal 11/12 on path 2
Power supply input terminal for output
terminal 11/12 on path 2
Common for output terminal (11/12 path 1)
Common for output terminal
(11/12 path 1)
Common for output terminal (11/12 path 2)
Common for output terminal
(11/12 path 2)
Output terminal 13 on path 1
Output terminal 13 for the redundant paths
Output terminal 13 on path 2
24V power supply input terminal for output
terminal 13 on path 1
Power supply input terminal for output terminal
13 on path 1
Consumption
current:75mA
Input voltage :
DC18V to DC27V *2)
24V power supply input terminal for output
terminal 13 on path 2
Power supply input terminal for output terminal
13 on path 2
Common for output terminal(13 path 1)
Common for output terminal (13 path 1)
Common for output terminal(13 path 2)
Common for output terminal (13 path 2)
Functional ground terminal
Connect to the functional ground
(The screw size is M3)