= Allowed
×
= Not permitted
]
Code Function Name Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE -FU -F -F -FU
Frequency Upper/Lower Limit and Jump Frequency
A061
Frequency upper limit setting
0.00 or "1st minimum frequency limit" to "maximum frequency" (Hz)
0.00 0.00 0.00 0.00 0.00
×○
A261
Frequency upper limit setting, 2nd motor
0.00 or "2nd minimum frequency limit" to "maximum frequency, 2nd motor" (Hz)
0.00 0.00 0.00 0.00 0.00
×○
A062
Frequency lower limit setting
0.00 or "start frequency" to "maximum frequency limit" (Hz)
0.00 0.00 0.00 0.00 0.00
×○
A262
Frequency lower limit setting, 2nd motor
0.00 or "start frequency" to "maximum frequency, 2nd motor limit" (Hz)
0.00 0.00 0.00 0.00 0.00
×○
A063
Jump (center) frequency setting 1
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
×○
A064
Jump (hysteresis) frequency width setting 1
0.00 to 10.00 (Hz)
0.50 0.50 0.50 0.50 0.50
×○
A065
Jump (center) frequency setting 2
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
×○
A066
Jump (hysteresis) frequency width setting 2
0.00 to 10.00 (Hz)
0.50 0.50 0.50 0.50 0.50
×○
A067
Jump (center) frequency setting 3
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
×○
A068
Jump (hysteresis) frequency width setting 3
0.00 to 10.00 (Hz)
0.50 0.50 0.50 0.50 0.50
×○
A069
Acceleration stop time frequency setting
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
×○
A070
Acceleration stop time frequency setting
0.0 to 60.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
PID Control
A071
PID function enable
00 (disabling), 01 (enabling), 02 (enabling inverted-data output)
00 00 00 00 00
×○
A072
PID proportional gain
0.2 to 5.0
1.0 1.0 1.0 1.0 1.0
○○
A073
PID integral time constant
0.0 to 999.9, 1000. to 3600.0 (s)
1.0 1.0 1.0 1.0 1.0
○○
A074
PID derivative gain
0.00 to 99.99, 100.0 (s)
0.00 0.00 0.00 0.00 0.00
○○
A075
PV scale conversion
0.01 to 99.99
1.00 1.00 1.00 1.00 1.00
×○
A076
PV source setting
00 (input via OI), 01 (input via O), 02 (external communication),
03 (pulse-string frequency input), 10 (operation result output)
00 00 00 00 00
×○
A077
Output of inverted PID deviation
00 (OFF), 01 (ON)
00 00 00 00 00
×○
A078
PID variation range
0.0 to 100.0 (%)
0.0 0.0 0.0 0.0 0.0
×○
A079
PID feed forward selection
00 (disabled), 01 (O input), 02 (OI input), 03 (O2 input)
00 00 00 00 00
×○
AVR
A081
AVR function select
00 (always on), 01 (always oɈ ), 02 (oɈ during deceleration)
00 00 02 00 02
×
×
A082
AVR voltage select
200 V class: 200, 215, 220, 230, 240 (V) 400 V class: 380, 400, 415, 440, 460, 480 (V)
400
230/460 200/400 200/400 200/400
×
×
Operation Mode and acceleration/
deceleration function
A085
Operation mode selection
00 (Normal operation)/ 01 (Energy-saving operation)/ 02 (Fuzzy operation) (*3)
00 00 00 00 00
×
×
A086
Energy saving mode tuning
0.1 to 100.0
50.0 50.0 50.0 50.0 50.0
○○
A092
Acceleration (2) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00 15.00 15.00 15.00 15.00
○○
A292
Acceleration (2) time setting, 2nd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00 15.00 15.00 15.00 15.00
○○
A392
Acceleration (2) time setting, 3rd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00 15.00 15.00 15.00 15.00
○○
A093
Deceleration (2) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00 15.00 15.00 15.00 15.00
○○
A293
Deceleration (2) time setting, 2nd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00 15.00 15.00 15.00 15.00
○○
A393
Deceleration (2) time setting, 3rd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00 15.00 15.00 15.00 15.00
○○
External frequency adjustment
A094
Select method to switch to Acc2/Dec2 proÞ le
00 (switching by 2CH terminal), 01 (switching by setting),
02 (switching only when rotation is reversed)
00 00 00 00 00
××
A294
Select method to switch to Acc2/Dec2,
2nd motor
00 (switching by 2CH terminal), 01 (switching by setting),
02 (switching only when rotation is reversed)
00 00 00 00 00
××
A095
Acc1 to Acc2 frequency transition point
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
××
A295
Acc1 to Acc2 frequency transition point,
2nd motor
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
××
A096
Dec1 to Dec2 frequency transition point
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
××
A296
Dec1 to Dec2 frequency transition point,
2nd motor
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
××
A097
Acceleration curve selection
00 (linear), 01 (S curve), 02 (U curve), 03 (inverted-U curve), 04 (EL-S curve)
00 00 00 00 00
××
A098
Deceleration curve selection
00 (linear), 01 (S curve), 02 (U curve), 03 (inverted-U curve), 04 (EL-S curve)
00 00 00 00 00
××
A101
OI-L input active range start frequency
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
×○
A102
OI-L input active range end frequency
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
×○
A103
OI-L input active range start current
0. to "[OI]-[L] input active range end current" (%)
20. 20. 20. 20. 20.
×○
A104
OI-L input active range end current
"[OI]-[L] input active range start current" to 100. (%)
100. 100. 100. 100. 100.
×○
A105
OI-L input start frequency enable
00 (external start frequency), 1 (0 Hz)
00 00 00 00 00
×○
A111
O2-L input active range start frequency
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) (*3)
0.00 0.00 0.00 0.00 0.00
×○
A112
O2-L input active range end frequency
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) (*3)
0.00 0.00 0.00 0.00 0.00
×○
A113
O2-L input active range start voltage
-100. to 02 end-frequency rate (%)
-100. -100. -100. -100. -100.
×○
A114
O2-L input active range end voltage
"02 start-frequency rate" to 100. (%)
100. 100. 100. 100. 100.
×○
Acceleration
and
deceleration
A131
Acceleration curve constants setting
01 (smallest swelling) to 10 (largest swelling)
02 02 02 02 02
×○
A132
Deceleration curve constants setting
01 (smallest swelling) to 10 (largest swelling)
02 02 02 02 02
×○
Operation-target frequency
A141
Operation-target frequency selection 1
00 (digital operator), 01 (keypad potentiometer), 02 (input via O), 03 (input via OI),
04 (external communication), 05 (option 1), 06 (option 2), 07 (pulse-string frequency input)
02 02 02 02 02
×○
A142
Operation-target frequency selection 2
00 (digital operator), 01 (keypad potentiometer), 02 (input via O), 03 (input via OI),
04 (external communication), 05 (option 1), 06 (option 2), 07 (pulse-string frequency input)
03 03 03 03 03
×○
A143
Operator selection
00 (addition: A141 + A142), 01 (subtraction: A141 - A142), 02 (multiplication: A141 x A142)
00 00 00 00 00
×○
A145
Frequency to be added
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 0.00 0.00 0.00 0.00
×○
A146
Sign of the frequency to be added
00 (frequency command + A145), 01 (frequency command - A145)
00 00 00 00 00
×○
Acceleration
and deceleration
A150
EL-S-curve acceleration ratio 1
0. to 50. (%)
25. 25. 25. 25. 25.
××
A151
EL-S-curve acceleration ratio 2
0. to 50. (%)
25. 25. 25. 25. 25.
××
A152
EL-S-curve deceleration ratio 1
0. to 50. (%)
25. 25. 25. 25. 25.
××
A153
EL-S-curve deceleration ratio 2
0. to 50. (%)
25. 25. 25. 25. 25.
××
(*1) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz) (*2) -120. to -100., -99.9 to 0.00 to 99.99 ,100.0 to 120.0 (Hz)
(*3) SJ700D (VT mode):00 (Normal operation), 01 (Energy saving operation)
16