A GROUP: STANDARD FUNCTIONS
[◯
= Allowed
×
= Not permitted
]
Code Function Name Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE -FU -F -F -FU
Basic settings
A001
Frequency source setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block),
02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2),
06 (pulse-string input), 07 (easy sequence), 10 (operation function result)
01 01 02 01 02
××
A002
Run command source setting
01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2)
01 01 02 01 02
××
A003
Base frequency setting
30. to "maximum frequency " (Hz)
50. 60. 60. 50. 60.
××
A203
Base frequency setting, 2nd motor
30. to "maximum frequency, 2nd motor" (Hz)
50. 60. 60. 50. 60.
××
A303
Base frequency setting, 3rd motor
30. to "maximum frequency, 3rd motor" (Hz)
50. 60. 60. 50. 60.
××
A004
Maximum frequency setting
"base frequency" to 400. (Hz) (*2)
50. 60. 60. 50. 60.
××
A204
Maximum frequency setting, 2nd motor
"base frequency, 2nd motor" to 400. (Hz) (*2)
50. 60. 60. 50. 60.
××
A304
Maximum frequency setting, 3rd motor
"base frequency, 3rd motor" to 400. (Hz) (*2)
50. 60. 60. 50. 60.
××
Analog input and others
A005
[AT] selection
00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1), 03
(switching between OI terminal and keypad potentiometer) (*1), 04 (switching
between O2 and keypad potentiometer) (*1)
00 00 00 00 00
××
A006
[O2] selection
00 (single), 01 (auxiliary frequency input via O and OI terminals) (nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible), 03 (disabling
O2 terminal)
03 03 03 03 03
××
A011
O-L input active range start frequency
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.00 0.00 0.00 0.00 0.00
×○
A012
O-L input active range end frequency
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.00 0.00 0.00 0.00 0.00
×○
A013
O-L input active range start voltabe
0. to "[O]-[L] input active range end voltage" (%)
0. 0. 0. 0. 0.
×○
A014
O-L input active range end voltabe
"[O]-[L] input active range start voltage" to 100. (%)
100. 100. 100. 100. 100.
×○
A015
O-L input active range start frequency selection
00 (external start frequency), 01 (0 Hz)
01 01 01 01 01
×○
A016
External frequency Þ lter time constant
1. to 30. or 31. (500 ms Þ lter ±0.1 Hz with hysteresis)
31. 31. 31. 31. 31.
×○
A017
Easy sequence function selection
00 (disabling), 01 (enabling)
SJ700D: 00 (disabling), 01 (PRG terminal), 02 (always on)
00 00 00 00 00
××
Multispeed operation and Jogging
A019
Multispeed operation selection
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable with 7 terminals)
00 00 00 00 00
××
A020
Multispeed frequency setting
0.00 or “start frequency” to “maximum frequency” (Hz)
0.00 0.00 0.00 0.00 0.00
○○
A220
Multispeed frequency setting, 2nd motor
0.00 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.00 0.00 0.00 0.00 0.00
○○
A320
Multispeed frequency setting, 3rd motor
0.00 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.00 0.00 0.00 0.00 0.00
○○
A021
-
A035
Multispeed 1-15 setting
0.00 or “start frequency” to “n-th maximum frequency” (Hz)
0.00 0.00 0.00 0.00 0.00
○○
A038
Jog frequency setting
"Start frequency" to 9.99 (Hz)
1.00 1.00 1.00 1.00 1.00
○○
A039
Jog stop mode
00 (free-running after jogging stops [disabled during operation]), 01 (deceleration
and stop after jogging stops [disabled during operation]), 02 (DC braking after
jogging stops [disabled during operation]), 03 (free-running after jogging stops
[enabled during operation]), 04 (deceleration and stop after jogging stops [enabled
during operation]), 05 (DC braking after jogging stops [enabled during operation])
00 00 00 00 00
×○
V/f Characteristic
A041
Torque boost method selection
00 (Manual torque boost) / 01 (Automatic torque boost)
00 00 00 00 00
××
A241
Torque boost method selection, 2nd motor
00 (Manual torque boost) / 01 (Automatic torque boost)
00 00 00 00 00
××
A042
Manual torque boost value
0.0 to 20.0 (%)
1.0 1.0 1.0 1.0 1.0
○○
A242
Manual torque boost value, 2nd motor
0.0 to 20.0 (%)
1.0 1.0 1.0 1.0 1.0
○○
A342
Manual torque boost value, 3rd motor
0.0 to 20.0 (%)
1.0 1.0 1.0 1.0 1.0
○○
A043
Manual torque boost frequency adjustment
0.0 to 50.0 (%)
5.0 5.0 5.0 5.0 5.0
○○
A243
Manual torque boost frequency adjustment, 2nd motor
0.0 to 50.0 (%)
5.0 5.0 5.0 5.0 5.0
○○
A343
Manual torque boost frequency adjustment, 3rd motor
0.0 to 50.0 (%)
5.0 5.0 5.0 5.0 5.0
○○
A044
V/F characteristic curve selection,
1st motor (*5)
00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control),
04 (0Hz-range sensorless vector), 05 (vector with sensor)
00 00 00 00 00
××
A244
V/F characteristic curve selection,
2nd motor (*5)
00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control),
04 (0Hz-range sensorless vector)
00 00 00 00 00
××
A344
V/F characteristic curve selection, 3rd motor
00 (VC), 01 (VP)
00 00 00 00 00
××
A045
V/f gain setting
20. to 100. (%)
100. 100. 100. 100. 100.
○○
A046
Voltage compensation gain setting
for automatic torque boost. 1st motor
0. to 255.
100. 100. 100. 100. 100.
○○
A246
Voltage compensation gain setting
for automatic torque boost, 2nd motor
0. to 255.
100. 100. 100. 100. 100.
○○
A047
Slippage compensation gain setting
for automatic torque boost, 1st motor
0. to 255.
100. 100. 100. 100. 100.
○○
A247
Slippage compensation gain setting
for automatic torque boost, 2nd motor
0. to 255.
100. 100. 100. 100. 100.
○○
DC Braking
A051
DC braking enable
00 (disabling), 01 (enabling), 02 (set frequency only)
00 00 00 00 00
×○
A052
DC braking frequency setting
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.50 0.50 0.50 0.50 0.50
×○
A053
DC braking wait time
0.0 to 5.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
A054
DC braking force during deceleration
SJ700/SJ700D (CT): 0. to 100. (%) <75 to 132kW:0. to 80./185kW and over:0. to 35.>
SJ700D (VT): 0. to 70. (%) <75 to 132kW:0. to 50.>
SJ700B: 0. to 70. (%) <90kW and over:0. to 50.>
0 0 0 0 20.0
×○
A055
DC braking time for deceleration
0.0 to 60.0 (s)
0.0 0.0 0.0 0.0 0.5
×○
A056
DC braking/edge or level detection for [DB] input
00 (edge operation), 01 (level operation)
01 01 01 01 01
×○
A057
DC braking force for starting
SJ700/SJ700D (CT): 0. to 100. (%) <75 to 132kW:0. to 80./185kW and over:0. to 35.>
SJ700D (VT): 0. to 70. (%) <75 to 132kW:0. to 50.>
SJ700B: 0. to 70. (%) <90kW and over:0. to 50.>
0. 0. 0. 0. 0.
×○
A058
DC braking time for starting
0.0 to 60.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
A059
DC braking carrier frequency setting
SJ700/SJ700D (CT): 0.5 to 15.0(kHz) <75 to 132kW:0.5 to 10.0/185kW and over:0.5 to 3.0>
SJ700D (VT): 0.5 to
12.0 (kHz)
<75 to 132kW:0.5 to 8.0>
SJ700B: 0.5 to 12.0 (kHz) <90kW and over:0.5 to 8.0>
5.0
<75 to 132kW:3.0>
3.0 3.0
××
(*1) This setting is valid only when the OPE-SR is connected. (*2) 4000HF:30. to 120. (Hz)
(*3) Derating is applied for SJ700B. Please consult technician at Hitachi or its distributor before use. (*4) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz)
(*5) SJ700D (VTmode):00 (VC), 01 (VP), 02 (free V/F), 03 (sensorless vector control)