= Allowed
×
= Not permitted
]
Code Function Name Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE -FU -F -F -FU
Communication
function
C076
Selection of the operation after
communication error
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring
errors), 03 (stopping the motor after free-running), 04 (decelerating and stopping
the motor)
02 02 02 02 02
×○
C077
Communication timeout limit before tripping
0.00 to 99.99 (s)
0.00 0.00 0.00 0.00 0.00
×○
C078
Communication wait time
0. to 1000. (ms)
0. 0. 0. 0. 0.
×○
C079
Communication mode selection
00 (ASCII), 01 (Modbus-RTU)
00 00 00 00 00
×○
Adjustment
C081
O input span calibration
0. to 9999., 1000 to 6553 (10000 to 65530)
Factory set
○○
C082
OI input span calibration
0. to 9999., 1000 to 6553 (10000
〜
65530)
○○
C083
O2 input span calibration
0. to 9999., 1000 to 6553 (10000
〜
65530)
○○
C085
Thermistor input tuning
0.0 to 999.9, 1000.
○○
C091
Debug mode enable
(Do not change this parameter, which is intended for factory adjustment.)
00 00 00 00 00
○○
Others
C101
UP/DOWN memory mode selection
00 (not storing the frequency data), 01 (storing the frequency data)
00 00 00 00 00
×○
C102
Reset mode selection
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is oɈ ),
02 (enabling resetting only upon tripping [resetting when RS is on]),
03 (resetting only trip)
00 00 00 00 00
○○
C103
Restart mode after reset
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (restarting with active matching frequency)
00 00 00 00 00
×○
Meter adjustment
C105
FM gain adjustment
50. to 200. (%)
100. 100. 100. 100. 100.
○○
C106
AM gain adjustment
50. to 200. (%)
100. 100. 100. 100. 100.
○○
C107
AMI gain adjustment
50. to 200. (%)
100. 100. 100. 100. 100.
○○
C109
AM bias adjustment
0. to 100. (%)
0. 0. 0. 0. 0.
○○
C110
AMI bias adjustment
0. to 100. (%)
20. 20. 20. 20. 20.
○○
Terminal
C111
Overload setting (2)
SJ700/SJ700D (CT):0.0 to 2.00 x "rated current" (A)
<75kW and over:0.0 to 1.80 x "rated current">
SJ700D (VT)/SJ700B:0.0 to 1.50 x "rated current" (A)
Rated current of
inverter x 1.00
○○
Adjustment
C121
O input zero calibration
0. to 9999., 1000 to 6553 (10000 to 65530)
Factory set
○○
C122
OI input zero calibration
0. to 9999., 1000 to 6553 (10000 to 65530)
○○
C123
O2 input zero calibration
0. to 9999., 1000 to 6553 (10000 to 65530)
○○
Output terminal operation function
C130
Output 11 on-delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C131
Output 11 oɈ -delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C132
Output 12 on-delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C133
Output 12 oɈ -delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C134
Output 13 on-delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C135
Output 13 oɈ -delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C136
Output 14 on-delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C137
Output 14 oɈ -delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C138
Output 15 on-delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C139
Output 15 oɈ -delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C140
Output RY on-delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C141
Output RY oɈ -delay time
0.0 to 100.0 (s)
0.0 0.0 0.0 0.0 0.0
×○
C142
Logical output signal 1 selection 1
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C143
Logical output signal 1 selection 2
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C144
Logical output signal 1 operator selection
00 (AND), 01 (OR), 02 (XOR)
00 00 00 00 00
×○
C145
Logical output signal 2 selection 1
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C146
Logical output signal 2 selection 2
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C147
Logical output signal 2 operator selection
00 (AND), 01 (OR), 02 (XOR)
00 00 00 00 00
×○
C148
Logical output signal 3 selection 1
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C149
Logical output signal 3 selection 2
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C150
Logical output signal 3 operator selection
00 (AND), 01 (OR), 02 (XOR)
00 00 00 00 00
×○
C151
Logical output signal 4 selection 1
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C152
Logical output signal 4 selection 2
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C153
Logical output signal 4 operator selection
00 (AND), 01 (OR), 02 (XOR)
00 00 00 00 00
×○
C154
Logical output signal 5 selection 1
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C155
Logical output signal 5 selection 2
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C156
Logical output signal 5 operator selection
00 (AND), 01 (OR), 02 (XOR)
00 00 00 00 00
×○
C157
Logical output signal 6 selection 1
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C158
Logical output signal 6 selection 2
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 00 00 00 00
×○
C159
Logical output signal 6 operator selection
00 (AND), 01 (OR), 02 (XOR)
00 00 00 00 00
×○
Input terminal response
C160
Input terminal response time setting 1
0. to 200. (×2ms)
1 1 1 1 1
×○
C161
Input terminal response time setting 2
0. to 200. (×2ms)
1 1 1 1 1
×○
C162
Input terminal response time setting 3
0. to 200. (×2ms)
1 1 1 1 1
×○
C163
Input terminal response time setting 4
0. to 200. (×2ms)
1 1 1 1 1
×○
C164
Input terminal response time setting 5
0. to 200. (×2ms)
1 1 1 1 1
×○
C165
Input terminal response time setting 6
0. to 200. (×2ms)
1 1 1 1 1
×○
C166
Input terminal response time setting 7
0. to 200. (×2ms)
1 1 1 1 1
×○
C167
Input terminal response time setting 8
0. to 200. (×2ms)
1 1 1 1 1
×○
C168
Input terminal response time setting FW
0. to 200. (×2ms)
1 1 1 1 1
×○
other
C169
Multistage speed/position determination time
0. to 200. (×10ms)
0 0 0 0 0
×○
21