Chapter 4 Explanation of Functions 
 
4 - 126 
(xii) 0B command: This command recalculates the constants set in the inverter. 
This command must be issued when the base frequency or the setting of parameter "H***" has been 
changed for the RS485 communication. 
- Transmission frame 
Frame format 
STX Station No. Command BCC  CR 
 
 Description Data size Setting 
STX  Control code (Start of TeXt)  1 byte  STX (0x02) 
Station No. 
Station number of control-target 
inverter 
2 bytes  01 to 32 
Command  Command to be transmitted  2 bytes  0B 
BCC  Block check code  2 bytes 
XOR of the items from "Station No." to "Data." 
See Item (3) of this section. 
CR  Control code (Carriage Return)  1 byte  CR (0x0D) 
 
- Response frame 
Positive response: See Item (2)-(i) of this section. 
Negative response: See Item (2)-(ii) of this section.