Chapter 8 List of Data Settings 
 
8 - 6 
 
Code  Function name  Monitored data or setting  Default 
Setting 
during 
operation 
(allowed or 
not) 
Change 
during 
operation 
(allowed or 
not) 
Page
b001  Selection of restart mode 
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03 (tripping 
after deceleration and stopping with matching frequency), 04 (restarting with active 
matching frequency) 
00 
¯  { 
b002 
Allowable under-voltage power failure 
time 
0.3 to 25.0 (s)  1.0 
¯  { 
b003  Retry wait time before motor restart  0.3 to 100.0 (s)  1.0 
¯  { 
b004 
Instantaneous power 
failure/under-voltage trip alarm enable 
00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating to stop)  00 
¯  { 
b005 
Number of restarts on power 
failure/under-voltage trip events 
00 (16 times), 01 (unlimited)  00 
¯  { 
4-33
b006  Phase loss detection enable  00 (disabling), 01 (enabling)  00 
¯  { 
4-36
b007  Restart frequency threshold  0.00 to 99.99, 100.0 to 400.0 (Hz)  0.00 
¯  { 
b008  Selection of retry after tripping 
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03 (tripping 
after deceleration and stopping with matching frequency), 04 (restarting with active 
matching frequency) 
00 
¯  { 
b009  Selection of retry after undervoltage  00 (16 times), 01 (unlimited)  00 
¯  { 
b010 
Selection of retry count after 
overvoltage or overcurrent 
1 to 3 (times)  3 
¯  { 
Restart after instantaneous power failure or tripping 
b011  Retry wait time after tripping  0.3 to 100.0 (s)  1.0 
¯  { 
4-33
b012 
Electronic thermal setting (calculated 
within the inverter from current output) 
0.20 x "rated current" to 1.00 x "rated current" (A) 
Rated current 
of inverter 
¯  { 
b212 
Electronic thermal setting (calculated 
within the inverter from current output), 
2nd motor 
0.20 x "rated current" to 1.00 x "rated current" (A) 
Rated current 
of inverter 
¯  { 
b312 
Electronic thermal setting (calculated 
within the inverter from current output), 
3rd motor 
0.20 x "rated current" to 1.00 x "rated current" (A) 
Rated current 
of inverter 
¯  { 
b013  Electronic thermal characteristic  00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free setting) 01 
¯  { 
b213 
Electronic thermal characteristic, 2nd 
motor 
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free setting) 01 
¯  { 
b313 
Electronic thermal characteristic, 3rd 
motor 
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free setting) 01 
¯  { 
4-37
b015 
Free setting, electronic thermal 
frequency (1) 
0. to 400. (Hz)  0. 
¯  { 
b016 
Free setting, electronic thermal current 
(1) 
0.0 to rated current (A)  0.0 
¯  { 
b017 
Free setting, electronic thermal 
frequency (2) 
0. to 400. (Hz)  0. 
¯  { 
b018 
Free setting, electronic thermal current 
(2) 
0.0 to rated current (A)  0.0 
¯  { 
b019 
Free setting, electronic thermal 
frequency (3) 
0. to 400. (Hz)  0. 
¯  { 
Electronic thermal function 
b020 
Free setting, electronic thermal current 
(3) 
0.0 to rated current (A)  0.0 
¯  { 
4-38
b021  Overload restriction operation mode 
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling during 
constant speed), 03 (enabling during acceleration and deceleration (increasing the 
speed during regeneration)) 
01 
¯  { 
b022  Overload restriction setting  0.20 x "rated current" to 1.50 x "rated current" (A) 
Rated 
current of 
inverter x 
1.20 
¯  { 
b023 
Deceleration rate at overload 
restriction 
0.10 to 30.00 (s)  1.00 
¯  { 
b024 
Overload restriction operation mode 
(2) 
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling during 
constant speed), 03 (enabling during acceleration and deceleration (increasing the 
speed during regeneration)) 
01 
¯  { 
b025  Overload restriction setting (2)  0.20 x "rated current" to 1.50 x "rated current" (A) 
Rated 
current of 
inverter x 
1.20 
¯  { 
b026 
Deceleration rate at overload restriction 
(2) 
0.10 to 30.00 (s)  1.00 
¯  { 
4-39
b027  Overcurrent suppression enable  00 (disabling), 01 (enabling)  01 
¯  { 
4-40
b028 
Active frequency matching, scan start 
frequency 
0.20 x "rated current" to 1.50 x "rated current" (A) 
Rated current 
of inverter 
¯  { 
b029 
Active frequency matching, scan-time 
constant 
0.10 to 30.00 (s)  0.50 
¯  { 
Overload restriction and overcurrent restraint 
b030 
Active frequency matching, restart 
frequency select 
00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set frequency)  00 
¯  { 
4-33
Software 
lock 
b031  Software lock mode selection 
00 (disabling change of data other than "b031" when SFT is on), 01 (disabling change 
of data other than "b031" and frequency settings when SFT is on), 02 (disabling 
change of data other than "b031"), 03 (disabling change of data other than "b031" and 
frequency settings), 10 (enabling data changes during operation) 
01 
¯  { 
4-51