Chapter 2 Installation and Wiring 
 
2 - 14 
 
Terminal layout  Inverter model 
 
 
 
SJ700B-075,110HFF 
 
R0 and T0: M4 
Ground terminal: M6 
Other terminals: M6 
RB 
R 
(L1) 
S 
(L2) 
T 
(L3) 
PD 
(+1) 
P 
(+) 
N 
(-) 
U 
(T1) 
V 
(T2) 
W 
(T3) 
R0  T0 
G G 
 
 
SJ700B-150HFF 
 
R0 and T0: M4 
Ground terminal: M6 
Other terminals: M6 
RB 
R 
(L1) 
S 
(L2) 
T 
(L3) 
PD 
(+1) 
P 
(+) 
N 
(-) 
U 
(T1) 
V 
(T2) 
W 
(T3) 
R0  T0 
G G 
 
 
SJ700B-185 to 
SJ700B-300HFF 
 
R0 and T0: M4 
Ground terminal: M6 
Other terminals: M6 
Disabling the EMC filter   
(factory setting :xFF2,xFUF2)
[Method of enabling/disabling the EMC filter 
Enabling the EMC filter 
(factory setting :xFEF2) 
Jumper connecting 
terminals PD and P 
Ground terminal with 
jumper (shaded in the 
figure) to enable/disable the 
EMC filter function 
When not using the DCL, 
do not remove the jumper 
from terminals PD and P. 
[Method of enabling/disabling the EMC filter function] 
Charge lamp 
Jumper connecting 
terminals PD and P 
Ground terminal with 
jumper (shaded in the 
figure) to enable/disable the 
EMC filter function 
When not using the DCL, 
do not remove the jumper 
from terminals PD and P. 
 