Manual torque boost value
Can boost starting torque
between 0 and 20% above
normal V/f curve,
range is 0.0 to 20.0%
Manual torque boost value, 2
nd
motor
Manual torque boost
frequency
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
Manual torque boost
frequency,
2
nd
motor
Four available V/f curves;
Constant torque
Reduced torque (1.7)
Free V/F
Sensorless vector (SLV)
V/f characteristic curve,
2
nd
motor
Sets voltage gain of the inverter,
range is 20. to 100.%
Voltage compensation gain for
automatic torque boost
Sets voltage compensation gain
under automatic torque boost,
range is 0. to 255.
Voltage compensation gain for
automatic torque boost, 2
nd
motor
Slip compensation gain for
automatic torque boost
Sets slip compensation gain
under automatic torque boost,
range is 0. to 255.
Slip compensation gain for
automatic torque boost, 2
nd
motor
Three options; select codes:
Disable
Enable during stop
Frequency detection
The frequency at which DC
braking begins,
range is from the start frequency
() to 60Hz
The delay from the end of
controlled deceleration to start of
DC braking (motor free runs until
DC braking begins),
range is 0.0 to 5.0 sec.
DC braking force for
deceleration
Level of DC braking force,
settable from 0 to 100%
DC braking time for
deceleration
Sets the duration for DC braking,
range is from 0.0 to 60.0
seconds
DC braking / edge or level
detection for [DB] input
Two options; select codes:
Edge detection
Level detection