Chapter 8 PROFINET Specification
43
(*) V2 is boolean variables are combined in two octets. Refer to the specification of PROFIdrive for
detail.
The error codes are the following.
Additional info
= Error value 2
Impermissible
parameter number
Access to unavailable parameter
Parameter value cannot
be changed
Change access to a parameter value
that cannot be changed
Low or high limit
exceeded
Change access with value outside the
value limits
Access to unavailable subindex of array
or string parameter. Shall not be used
for single parameters
Access with subindex to non-indexed
Parameter
Change access with value that does not
match the data type of the parameter
Setting not permitted
(may only be reset)
Change access with value unequal to 0
where this is not permitted
Description element
cannot be Changed
Change access to a description element
that cannot be changed
No description data
available
Access to unavailable description
(parameter value is available)
Change access without rights to change
Parameters
Access to text array that is not available
(parameter value is available)
Request cannot be
executed because of
operating state
Access is temporarily not possible for
reasons that are not specified in detail.
When the parameter of WJ200 / WL200
is accessed, please check whether the
inverter can accept change access.
Change access with a value that is
within the value limits, but is not
permissible for other long-term reasons
(parameter with defined single values)
The length of the current response
exceeds the maximum transmittable
length of the response transport block.
In case of a multi parameter request,
the response block was shortened by
omitting of parameter requests.