EasyManua.ls Logo

Hiwin E1 Series - Freerun; SDO Abort Code

Hiwin E1 Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E1 Series Servo Drive EtherCAT(CoE) Communications Command Manual EtherCAT Communication
HIWIN MIKROSYSTEM Corp. 2-11
MD08UE01-1812
2.5.2 FreeRun
FreeRun is started by the local timer interrupt of the drive. The local cycle runs independently of the
communication cycle and the master cycle.
Figure 2.5.2.1
Note: The PDO transmission interval should not be less than 250 μs.
2.6 SDO abort code
When SDO communication error occurs, SDO abort code is returned. The supported SDO abort codes
are listed in Table 2.6.1.
Table 2.6.1
Value Descritpion
06010000h
Unsupported access to an object
06010002h
Attempt to write to a read-only object
06020000h
The object does not exist in the object dictionary
06040042h
Number and length of the objects to be mapped would exceed PDO length
06090030h
Value range of parameter exceeded (only for write access)

Other manuals for Hiwin E1 Series

Related product manuals