EasyManua.ls Logo

HMS Anybus AS-Interface Master - Page 8

Default Icon
19 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
How to configure an Anybus AS-Interface Master module
SCM-7032-036
Rev 1.02
The figure below shows an example; in this case an AS-Interface Master to Modbus-TCP Slave X-gateway is
used. 20 bytes of I/O data on the Modbus-TCP side and 312 bytes of I/O data on the AS-Interface side are
configured. Also byte mode is used in this configuration.
Note: The Input and Output data size is always set to 312 bytes and cannot be changed.
Data Representation:
This mode can be set to Byte Mode
or Nibble Mode.
Figure 4 The X-gateway configuration.
The next step is to set the X-gateway in running mode.
Running: AS-Interface network is
running and exchanging data.
Idle DE Active: AS-Interface
network is idle, but the
communication is still active.
Idle DE Inactive: AS-Interface
network is idle and no data exchange
messages are issued.
Figure 5 Changing Operation mode of the X-gateway.
Choosing 9 from the main menu the X-gateway can be set to Running, Idle DE Active or Idle DE Inactive.
Set the Operation Mode to Running.
www.anybus.com HMS Industrial Networks AB
Page 8 (19)

Related product manuals