How to configure an Anybus AS-Interface Master module
SCM-7032-036
Rev 1.02
www.anybus.com HMS Industrial Networks AB
Page 9 (19)
5 AS-Interface configuration
The AS-Interface Master configuration can be done in several ways.
1 The Configuration Button enables the auto configuration as described in section 5.1 Configuration using
the Configuration Button.
2 The Terminal Interface can also be used to configure the AS-Interface Master as described in section 5.2
Configuration using the Terminal Interface. Using this alternative it is possible to change the slave
parameters.
3 The configuration can also be done by using mailbox commands. Please see the Master Fieldbus
Appendix. Note: This alternative is usable only by Anybus-M AS-Interface Master and Anybus-M PCI AS-
Interface Master.
In the end of this chapter, section 5.3 Memory Mapping, the memory mapping is described in detail.
5.1 Configuration using the Configuration Button
This alternative assumes the AS-Interface network is connected to the Anybus Master. Please follow the
steps below.
1 Changing to Configuration mode using the Configuration Button
This is done by pressing the Configuration Button for less than 2 seconds, which will toggle the mode
between Configuration and Protected mode. The Module Status/MS LED is solid green in Configuration
mode.
2 Pressing the Configuration Button to upload and save the network configuration
Push and hold the Configuration Button for more than 5 seconds, this will enable the Auto Configuration.
3 Changing to Protected mode
Press the Configuration button again for less than 2 seconds to change the mode to Protected mode.
4 Network running
If the configuration is successful the network is now online and running. The Running/RUN LED is now
solid green and Network Status/NS LED and Module Status LED are flashing green. Auto prog./AUP LED
is off indicating no error.