38
1.
Make sure they are facing in the right direction,
since you can’t put them on or change their
Flare Nut
Copper Pipe
2. Remove the PVC tape from the ends of the
3.
The end of the pipe must extend beyond the
dimensions shown in the table at the upper right.
PIPING EXTENSION BEYOND FLARE FORM
Outer Diameter
of Pipe
(Inch/mm)
A (Inch/mm)
Min. Max.
Ø 0.25" (Ø6.35) 0.0275" (0.7) 0.05" (1.3)
Ø 0.375" (Ø9.52) 0.04" (1.0) 0.063" (1.6)
Ø 0.5" (Ø12.7) 0.04" (1.0) 0.07" (1.8)
Ø 0.63" (Ø16) 0.078" (2.0) 0.086" (2.2)
Flare Form
Pipe
A
4.
5.
6.
Inspect the end of the pipe for cracks and
Step 4: Connect the pipes.
When connecting refrigerant pipes, be careful not
to use excessive torque or deform the piping in
pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the
minimum bending radius is 4 inches.
4 in
Radius
Instructions for Connecting Piping to the Indoor
Unit
1. Align the center of the two pipes that you will
connect.
Indoor Unit Tubing Flare Nut Pipe
2.
hand.
3. Use a spanner to grip the nut on the unit tubing.
4.
tubing, use a torque wrench to tighten the
Torque Requirements table below. Loosen the
Refrigerant Piping Connection