1H/1C System (1 transformer)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
W Heat
G Fan
Heat-only System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24VAC common [3]
W Heat
Heat-only System (Series 20) [5]
R Series 20 valve terminal “R” [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Series 20 valve terminal “W
C 24VAC common [3]
W Series 20 valve terminal “B”
Heat-only System
(power open zone valve) [5]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
W Valve
C 24VAC common [3]
1H/1C System (2 transformers)
R Power (heating transformer) [1]
Rc Power (cooling transformer) [1]
Y Compressor contactor
C 24VAC common [3, 4]
W Heat
G Fan
Heat-only System with Fan
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24VAC common [3]
W Heat
G Fan
Cool-only System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
G Fan
1H/1C Heat Pump System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
O/B Changeover valve [7]
G Fan
W Do not use this terminal for heat pump
applications!
2H/1C Heat Pump System (TH3210U only)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
O/B Changeover valve [7]
G Fan
AUX Auxiliary heat
E Emergency heat
W Do not use this terminal for heat pump
applications!
Wiring heat pump systems
Wiring conventional systems: forced air and hydronics
NOTES
Wire specifications: Use 18 to 22-gauge thermostat wire. Shielded cable is not required.
[1] Power supply. Provide disconnect means and overload
protection as required.
[2] Move RSlider Tab on UWP to the R setting. For more
information, see “Setting Slider Tabs (built-in jumper)” on
page 3
[3] Optional 24VAC common connection.
[4] Common connection must come from cooling transformer.
[5] In ISU set Heat system type to Radiant Heat. Set number of
cool stages to 0.
[7] In Installer Setup, set changeover valve to O (for cool
changeover) or B (for heat changeover).

Other manuals for Honeywell Home T3 Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Home T3 Pro and is the answer not in the manual?

Honeywell Home T3 Pro Specifications

General IconGeneral
BrandHoneywell Home
ModelT3 Pro
CategoryThermostat
LanguageEnglish

Related product manuals