RM7888A 7800 SERIES RELAY MODULE
32-00214—01 2
FEATURES
Safety features:
Closed loop logic test.
—Dynamic input check.
Dynamic safety relay test.
Dynamic self-check logic.
Expanded safe-start check.
Internal hardware status monitoring.
Tamper resistant timing and logic.
Access for external electrical voltage checks.
Application flexibility.
Communication interface capability using Modbus.
First-out annunciation and system diagnostics are
provided by the optional Keyboard Display Module.
Five sequence information LEDs.
Interchangeable plug-in flame amplifiers.
Local or remote annunciation of RM7888A operation
and fault information.
Dependable, long-term operation provided by
microcomputer technology.
Nonvolatile memory for retaining history files and
sequencing status after loss of power.
Remote reset capability (optional).
Burner controller data:
Sequence status.
Sequence time.
—Hold status.
—Lockout/alarm status.
Flame signal strength.
Expanded annunciator status.
Total hours of operation.
Total cycles of operation.
Fault history of six most recent faults:
Cycles of operation at the time of the fault.
Expanded annunciator data at the time of the
fault.
Fault message and code.
Hours of operation at the time of the fault.
Sequence status at the time of the fault.
Sequence time at the time of the fault.
Diagnostic information:
Device type.
Flame amplifier type.
Flame failure response time.
Manufacturing code.
On/Off status of all line voltage digital inputs.
Software revision and version of RM7888A via
S7800 Keyboard Display Module.
Status of configuration jumpers.
SPECIFICATIONS
Electrical Ratings (see Table 1):
Voltage and Frequency: 120 Vac (+10/-15%), 50/60 Hz
(±10%).
Keyboard Display Module: 13.0 Vdc peak full wave recti-
fied (+20/-15%).
Power Dissipation:
RM7888A: 10W maximum.
Display Module: 3W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing: Total Connected Load: 20A maximum, type FRN or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40° F to +140° F [-40° C to +60° C].
Storage: -40° F to + 150° F [-40° C to +66° C].
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System using Dynamic self check or amplicheck ampli-
fiers with the appropriate flame detector. See form
number 65-0312 for Certificate Agreement.
Dimensions: See Fig. 1
Weight:
RM7888A: 1 pound, 10 ounces [737 grams], unpacked.
Keyboard Display Module: 4 ounces [113 grams],
unpacked.
Approvals:
Underwriters Laboratories Inc. Listed: File No. MP268,
Vol. 30. UL 37260730-2-5 / CSA C22.2 No. 60730-
2-5.
Factory Mutual Approved: Report No. 1V9A0.AF.
Swiss Re (formerly Industrial Risk Insurers): Acceptable.
Federal Communications Commission: Part 15, Class
B, Emissions.
Exida: IEC 61508:2010 Parts 1-7, SIL 3 capable.
EAC Russia

Other manuals for Honeywell 7800 SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell 7800 SERIES and is the answer not in the manual?

Honeywell 7800 SERIES Specifications

General IconGeneral
Model7800 SERIES
CategoryControl Unit
Frequency50/60 Hz
ApprovalsUL, CE
CommunicationCommunication Interface (Optional)

Related product manuals