Conductivity/Resistivity Analyzer/Controller
9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual 7/995-24
PARAMETER CHOICES or RANGE
(Default is underlined)
I/O setup: discrete control enabled
NO
YES
I/O setup: discrete control type for each available relay
PFT
DAT
O/F [on/off]
N/A
I/O setup: relay activation on alarm/control
ENERGIZE
DE-ENERGIZE
I/O setup: display unit of measure (conductivity only)
standard range models with cell constant
1:
uS (microSiemens per centimeter)
uSm (microSiemens per meter)
standard range models with cell constant of 10,25,or 50:
uS (microSiemens per centimeter) only
wide range models: automatially change from uS to mS
depending on cell constant; no selection available.
I/O setup: relay alarm assignments
ALM1 [alarm 1] default for Relay 1
ALM2 [alarm 2] default for Relay 2
ALM3 [alarm 3] default for Relay 3
ALM4 [alarm 4] default for Relay 4
A1/D [alarm 1 or diagnostic]
A2/D [alarm 2 or diagnostic]
A3/D [alarm 3 or diagnostic]
A4/D [alarm 4 or diagnostic]
A1/2 [alarm 1 or 2]
A3/4 [alarm 3 or 4]
12/D [alarm 1 or 2 or diagnostic]
AA/D [any alarm or diagnostic]
234D [alarm 2 or 3 or 4 or diagnostic]
RNGD [range switch or diagnostic]
AA [any alarm]
RNGS [range switch]
I/O setup: analog output basis [unless DE is enabled]
C1 [Cell 1 value]
C2 [Cell 2 value]
TMP1 [temperature value from Cell 1]
TMP2 [temperature value from Cell 2]
RATO [computed ratio:
Cell
Cell
1
2
]
%REJ [computed percent rejection:
()x1
1
2
100
Cell
Cell
]
%PSG [computed percent passage:
Cell
Cell
x
1
2
100
]
DIFF [computed difference:
Cell Cell12
]
CO2 [computed parts per million carbon dioxide -
standard range analyzers only]
configuration: retransmission output scaling
LINFIXEDRNG [linear fixed range]
always selected for
computed value
LINAUTORNG [linear auto range]
2DECADELOG
BI-LINEAR

Table of Contents