Installation and Operations Guide
|
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
73
Table 20 EXP (ge ne ric) te chnical data
Po wer A 24 VAC, 50-60 Hz, minimum 20 VA trans forme r is ne cessary to
powe r a s ingle EXP board. Trans forme r s haring is allowe d for
powe ring multiple EXPs . Binary outputs are powe re d through
se parate te rminals but may s hare the EXP controlle rs
transformer. If s hare d, the VA rating of the controlle rs trans forme r
must be increas e d to account for the additional load from the
binary outputs. See Single -point grounding” on page 25.
Fus e Ale rto n Part Numbe r: BT-2.0A-5X20
Type : Onboard 2 Amp GDB fas t-acting fus e (5mm X 20mm)
Inputs Jumpe r-sele ctable , 12-bit unive rs al inputs acce pt following input
signals:
The rmistor (3K or 10K ohm) or othe r re sis tive inputs (s oftware
scalable)
Dry contact
420 mA (no e xte rnal resis tor re quire d)
•05VDC
010 VDC
Up to 100Hz puls e inputs s upported ONLY on inputs 1, 2, and 3.
Binary o utputs Binary outputs rated 24 VAC @ 0.5 A. Each binary output has a
Hand-Off-Auto (H-O-A) s witch for manual override of programme d
command. Us e one or more is olate d trans forme rs to powe r BOs
se parately from the EXP board s upply power.
Analo g outputs Analog outputs are drive n by a pre cis ion D/A conve rte r and are
DIP-s witch configurable to provide e ithe r 0–10 VDC or 020 mA.
Each analog output has a Hand-Off-Auto s witch for manual
ove rride of programme d command. Analog outputs als o include a
pote ntiome te r for manually adjus ting the output in Hand mode .
Max. dimens ions 7.148" (181.56mm) H X 7.283" (181.98mm) W X 1.500"
(38.10mm) D.
Te rminatio ns Re movable, heade r-s tyle s crew te rminals .
Environmental 32–131°F (0–55°C). 095% RH, non-conde ns ing.
Communic atio ns Up to e ight EXPs can conne ct to a VLX/VLX-Platinum or ACM-
VLX over a s imple communications bus . Us e 18 AWG two
conductor twiste d s hie ld cable. Cable le ngths be twe e n
compone nts must not e xce e d 10ft (3.048 m).
Rating s Lis ted Unde rwrite rs Laboratory for Ope n Ene rgy Manage ment
Equipme nt (PAZX) under the UL S tandard for Safety 916.
Lis ting include s both U.S . and Canadian ce rtification.
EMC Dire ctive 89/336/EEC (Europe an CE Mark).
FCC Part 15, S ubpart J, Clas s A.