Installation and Operations Guide
|
ACM-VLX/VLX/EXP/AXM
74
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Table 21 AXM (ge neric) te chnical data
Po wer A 24 VAC, 50-60 Hz, minimum 20 VA trans forme r is ne cessary to
powe r a s ingle AXM board. Trans forme r s haring is allowed for
powe ring multiple AXMs . Binary outputs are powe re d through
se parate te rminals but may s hare the AXM controlle rs
transformer. If s hare d, the VA rating of the controlle rs trans forme r
must be increas e d to account for the additional load from the
binary outputs. See Single -point grounding” on page 25.
Fus e Ale rto n Part Numbe r: BT-2.0A-5X20
Type : Onboard 2 Amp GDB fas t-acting fus e (5mm X 20mm)
Inputs Jumpe r-sele ctable , 12-bit unive rs al inputs acce pt following input
signals:
The rmistor (3K or 10K ohm) or othe r re sis tive inputs (s oftware
scalable)
Dry contact
420 mA (no e xte rnal resis tor re quire d)
•05VDC
010 VDC
Up to 100Hz puls e inputs are supported ONLY on inputs 1, 2, and
3.
Binary o utputs Binary outputs rated 24 VAC @ 0.5 A. Each binary output has a
Hand-Off-Auto (H-O-A) s witch for manual override of programme d
command. Us e one or more is olate d trans forme rs to powe r BOs
se parately from the AXM board s upply powe r.
Analo g outputs Analog outputs are drive n by a pre cis ion D/A conve rte r and are
DIP-s witch configurable to provide e ithe r 0–10 VDC or 020 mA.
Each analog output has a Hand-Off-Auto s witch for manual
ove rride of programme d command. Analog outputs als o include a
pote ntiome te r for manually adjus ting the output in Hand mode .
Max. dime ns io ns 6.98" (176.5 mm) H X 4.95" (125.7 mm) W X 1.6"
(40.5 mm) D.
Te rminatio ns Re movable, heade r-s tyle s crew te rminals .
Environme ntal 32131°F (055°C). 095% RH, non-conde ns ing.
Communic atio ns Up to e ight AXMs can conne ct to a VLX/ACM-VLX ove r a s imple
communications bus . Us e 18 AWG two conductor twis te d s hie ld
cable . Cable lengths be twe e n compone nts mus t not e xce e d 10 ft.
(3.048 m).
Rating s Lis ted Unde rwrite rs Laboratory for Ope n Ene rgy Manageme nt
Equipme nt (PAZX) under the UL S tandard for Safety 916.
Lis ting include s both U.S . and Canadian ce rtification.
EN 60730-1 (Europe an CE Mark).
ICES-003 Is s ue 6.
FCC Part 15, S ubpart B, S e ction 15.107 and 15.109, Class B.