Appendix F: BACnet object and property reference
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
83
status -flags Bit s tring <Bit string> A four-pos ition bit s tring that indicate s the status of the
AV. If a s tatus bit =1, that s tatus is TRUE.
units
Enumerated Deg F Indicates the unit of me asure , in BACne t e ngine e ring
units , for the AV pre s e nt-value.
priority-array BACne t
PriorityArray
<Array of
BACne t
Prio rityVa lue >
NOT AVAILABLE IN AVs (0-7999). GENERAL
PURPOSE AVs ONLY. An array of prioritize d value s
(inde xe s 1-16) controlling the pre s e nt-value , inde x 1
having the highe st priority. The value with the highe s t
priority controls the pre s e nt-value. Pos s ible value s for
priority-array inde xe s are re al value s or NULL. A NULL
value indicate s no command is iss ue d at that priority
inde x.
relinquis h-de fault
REAL 0 NOT AVAILABLE IN AVs (0-7999). GENERAL
PURPOSE AVs ONLY. Default value to be use d for
present-value prope rty when all priority-array indexes
are NULL.
Table 28 Prope rtie s of VLX/ACM-VLX AV obje cts (Continue d)
Prope rty W Type Example Re marks