Installation and Operations Guide
|
ACM-VLX/VLX/EXP/AXM
84
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Properties of VLX/ACM-VLX BI objects
Table 29 Prope rtie s of the VLX/ACM-VLX BI obje ct
Prope rty W Type Example Re marks
de s cription
Characte r s tring Fan S tatus An e ditable de s cription of the obje ct’s location or
function.
e ve nt-s tate Enumerated NORMAL
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
BI 10 This prope rty cons ists of the Obje ct_Type prope rty and
the Object Ins tance , which is a nume ric code that
identifies the object of interest.
obje ct-name
ACM
-VLX
Characte r string EXP 7 BI 10/
AXM 7 BI 10
The Obje ct Name prope rty is writable whe n us ing the
ACM-VLX only and not in the VLX/VLX-Platinum.
obje ct-type Enumerated BI Indicate s a binary input (BI) object.
out-of-s e rvice
Boole an FALS E TRUE de couple s the pres e nt-value prope rty from the
physical input, and the pre s e nt-value doe s not track
furthe r phys ical input change s . While TRUE, the
present-value can be change d to any value to simulate
conditions for te s ting. FALS E indicate s that the pre s e nt-
value is tracking change s to the physical input.
polarity NORMAL
present-value
Logical s tate ACTIVE ACTIVE or INACTIVE. Writable only whe n out-of-s e rvice
= TRUE (s e e he re in).
reliability NO FAULT
DETECTED
Othe r possibility is UNRELIABLE_OTHER.
status -flags Bit s tring In alarm = 0,
fault = 0,
ove rridden =
0, out of
se rvice = 0
A four-pos ition bit s tring that indicate s the status of the
obje ct. If a s tatus bit =1, that status is TRUE.
active-text
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
inactive -te xt
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
change -of-state -time ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).
change -of-state -count ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).
time -of-s tate -count-
re s e t
ACM
-VLX
Turn ON to re s e t the change-of-s tate count. Will
automatically change back to OFF.
e lapsed-active-time Runtime in s e conds
time -of-active -time -
re s e t
Turn ON to re s e t the e laps e d-active -time prope rty. Will
automatically change back to OFF.