Installation and Operations Guide
|
Appendix F: BACnet object and property reference
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
85
Properties of VLX/ACM-VLX BO objects
Table 30 Prope rtie s of the VLX/ACM-VLX BO object
Prope rty W Type Example Re marks
de s cription
Characte r string Fan S tart/
Stop
An e ditable de s cription of the obje ct’s location or
function.
e ve nt-s tate Enumerated Normal If the obje ct doe s not s upport intrins ic reporting, the
value will be NORMAL.
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
BO 1 This prope rty cons is ts of the obje ct-type property and the
obje ct instance , which is a nume ric code that ide ntifie s
the object of interest.
obje ct-name
ACM
-VLX
Characte r string EXP 7 BO
01/
AXM 7 BO
01
The Obje ct Name prope rty is writable whe n us ing it in
the ACM-VLX only and not in the VLX/VLX-Platinum.
obje ct-type Enumerated BO
out-of-s e rvice
Boole an FALS E TRUE de couple s the pres e nt-value prope rty from the
physical output. While TRUE, the pres e nt-value can be
change d to any value to s imulate conditions for tes ting
without affe cting the actual phys ical output.
present-value
Enumerated INACTIVE Eithe r ACTIVE or INACTIVE. Note that a NULL value
can be written to the pre s e nt-value on data dis plays , but
the value is actually written to a priority-array prope rty.
The pre s e nt-value is the re s ult of the priority array.
minimum-on-time
Real 60 Enable s you to s e t anti-cycle limits for a BO in seconds.
This is carrie d out through priority-array inde x 6. For
e xample , by writing a value of 60 to the minimum-on-
time property of a BO, you s e t a minimum ON time of 60
se conds.
minimum-off-time
Real 60 Enable s you to s e t anti-cycle limits for a BO in seconds.
This is carrie d out through priority-array inde x 6. For
e xample , by writing a value of 60 to the minimum-off-
time prope rty of a BO, you s e t a minimum OFF time of
60 s e conds .
priority-array BACne t
PriorityArray
<Array of
BACne t
P rio rityVa lue >
A read-only array of prioritize d value s (1-16) controlling
the pre s e nt-value , priority 1 having the highe s t priority.
The value with the highest priority controls the pre se nt-
value . Poss ible values for priority-array inde xe s are
ACTIVE, INACTIVE, or NULL. A NULL value indicate s
no command is iss ue d at that priority le ve l.
reliability BACne t_ Re liability NO FAULT
DETECTED
Othe r possibility is UNRELIABLE_OTHER.
relinquis h-de fault
Enumerated INACTIVE De fault value us e d for present-value prope rty when all
priority array value s are NULL.
status -flags Bit s tring In alarm = 0,
fault = 0,
ove rridden =
0, out of
se rvice = 0
A four-pos ition bit s tring that indicate s the status of the
obje ct. If a s tatus bit =1, that status is TRUE.
active-text
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.