Wiring and Setting Up the System LION System
EN1Z-0921GE51 R0709
24
Wiring and Setting Up the System
General Safety Considerations
When connecting the CLLIONLC01 or LION I/O modules,
both VDE, National Electric Code (NEC) or equivalent,
and any local regulations concerning grounding and zero
voltage must be observed.
Electrical work should be carried out by a qualified
electrician.
The electrical connections must be made at the terminal
blocks. The corresponding connection diagrams are
located on the individual controller module and
I/O modules.
For Europe only: To comply with CE requirements,
devices with a voltage in the range of 50 ... 1000 VAC or
75 ... 1500 VDC, which are not provided with a supply
cord and plug or with other means for disconnection from
the supply having a contact separation of at least 3 mm
in all poles, must have the means for disconnection
incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
Disconnect the power supply before making connections
to or removing connections from terminals of controller or
I/O modules.
Do not use spare terminals as wiring support points.
Do not reconnect the power supply until you have
completed the installation.
Observe precautions for handling electrostatic sensitive
devices.
Wiring Push-in Terminals
The terminal sockets of the pluggable I/O modules are
available in versions (…82…) featuring convenient push-in
terminals for easy wiring. The CLIOP830A likewise features
push-in terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
0.14 … 1.50 mm
2
Solid conductor H05/07) V-U
0.25 … 1.50 mm
2
Stranded conductor H05(07) V-K
0.25 … 1.50 mm
2
Stranded conductor with wire end
ferrules (without plastic collar)
0.25 ... 1.50 mm
2
Stripping length
8.0 +1.0 mm
Table 22 Push-in terminals wiring specifications
Wiring Screw-Type Terminals
The terminal sockets of the pluggable I/O modules are also
available with screw-type terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
0.14 … 1.50 mm
2
Solid conductor H05/07) V-U
0.25 … 1.50 mm
2
Stranded conductor H05(07) V-K
0.25 … 1.50 mm
2
Stranded conductor with wire end
ferrules (without plastic collar)
0.25 ... 1.50 mm
2
Stripping length
11.0 +1.0 mm
Table 23 Screw-type terminals wiring specifications