Troubleshooting LION System
EN1Z-0921GE51 R0709
78
I/O Modules Troubleshooting
Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the …821, …822, …823 I/O modules.
Replace the problem I/O module with another module of the same kind.
If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.
If the problem is solved, this is an indication that the I/O module was defective.
For troubleshooting purposes, the following features can be used:
Power LED (all LION I/O modules)
Service LED (all LION 800 I/O modules)
Service button (pluggable LION I/O modules, only)
In addition, a module-specific troubleshooting may be necessary.
Power LED of I/O Modules
case Power LED Meaning Remedy
1 ON
I/O module is powered
No action necessary
2 OFF
No power
Check power supply
3 Flashing continuously
If the I/O module’s service LED is likewise
flashing, the I/O module is in the boot mode
Wait until rebooting (firmware
download) has been completed
Table 77 Power LED of I/O modules