LION System Troubleshooting
79 EN1Z-0921GE51 R0709
Service LED of I/O Modules
case Service LED Meaning Remedy
1
LED remains OFF after
power-up
If the power LED is also OFF, then
– Defective device hardware
Possible power supply problems, clock
problems, or defective processor
Replace hardware
2
LED is lit continuously after
first power-up
L
ONWORKS Bus I/O modules:
– Defective hardware
Panel Bus I/O modules:
I/O module has not yet been configured
by XCL8010
Boot loader is active
Failure during last firmware download
– Checksum error
L
ONWORKS Bus I/O modules:
Replace hardware
Panel Bus I/O modules:
Set the hex address to the position configured
with CARE
Ensure that I/O Bus switch S2 of XCL8010
Controller is set to position "Panel"
Check the Panel Bus wiring:
- Check for cable breaks
- Check for cable short-circuits
- If using separate transformers: Check ground
connection
Eliminate any mixture of Panel Bus I/Os and
LonWorks I/Os on same wire
Allow XCL8010 to configure I/O module
Unplug and replug the module
If problem persists, replace hardware
3
Alternating flash between
service LED and power LED
Panel Bus I/O modules, only:
Download error or application checksum error.
Boot loader is running
Panel Bus I/O modules, only:
Wait until rebooting (firmware download) has
been completed
4
LED flashes at power up,
goes OFF, and then is lit
continuously
L
ONWORKS Bus I/O modules, only:
The L
ONWORKS Bus I/O module lacks
application
Download application
5
LED repeatedly blinks
ON for 1 sec and
OFF for 1 sec
L
ONWORKS Bus I/O modules, only:
The L
ONWORKS Bus I/O module is
unconfigured, but has an application
Set module to configured mode
6
LED remains OFF after a
short ON duration
I/O module is configured and running normally
No action necessary
7
LED flashes continuously in
following pattern:
4 x ON/OFF followed by
pause
Sensor failure of analog input module
(in the case of L
ONWORKS Bus I/O modules,
this behavior can occur only if the appropriate
NV has been bound)
Check sensor or connection
Check sensor configuration
8
LED flashes continuously in
following pattern:
5 x ON/OFF followed by
pause
L
ONWORKS Bus I/O modules, only: LONWORKS
I/O Bus module has received the wink
command from network, physical outputs are
unaffected
No action necessary
9
LED flashes continuously in
following pattern:
6 x ON/OFF followed by
pause
Boot loader problem or hardware defect
Replace hardware
10
LED flashes continuously in
following pattern:
7 x ON/OFF followed by
pause
Communications failure
Check bus wiring
Check I/O Bus switch S2 of CLLIONLC01
Controller
Ensure that L
ONWORKS Bus I/O modules and
Panel Bus I/O modules are not sharing the same
bus
In case of Panel Bus I/O modules, only:
Check for incorrect HEX addresses (2 Panel Bus
I/O modules using the same HEX address)
In case of L
ONWORKS Bus I/O modules, only:
Check heartbeat
Table 78 Service LED of I/O modules