LION System Description of the CLLIONLC01
35 EN1Z-0921GE51 R0709
CLLIONLC01 Terminals
74
14
10 7
2
3
4
78
73
13
9 6
1
77
72
12
8 5
76
71
11
75
24
V~
24
V~
24
V~
24
V~ 0
LON
2
C- C-
C+ C+
LON
2
LON
1
LON
1
24
V~ 0
24
V~ 0
NC
24
V~0
COM
B
COM
B
COM
A
COM
A
SHIELD SHIELD
8 7 6
5
4 32 1
*
*Watch Dog
Relay
Fig. 48 Terminal assignment and internal connections of
the CLLIONLC01
Ter-
minal
Signal Comment
71, 75 COM a
2-wire communication bus
(LON/Panel Bus)
72, 76 COM b
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NC Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Table 28 Description of CLLIONLC01 terminals
Features
LONWORKS Interface and Terminals
The CLLIONLC01 Controller Module features
• An RJ45 socket serving as an interface
to connect laptops to the L
ONWORKS Bus
• LONWORKS terminals 11, 12, 13, and 14
to connect L
ONWORKS Bus I/O modules or other
L
ONWORKS devices to the CLLIONLC01 Controller or
other L
ONWORKS controllers.
687 354 21
11
12
13
14
LON
Fig. 49 LONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Pin Signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 … 8 Not used
Table 29 Signals of LONWORKS interface
LONWORKS Service LED and Button
The CLLIONLC01 is equipped with a LONWORKS service
button and corresponding L
ONWORKS Service LED (status:
yellow/OFF).
Fig. 50 LONWORKS service button (1) and service LED (2)
See also section "Troubleshooting" on page 74.