EasyManua.ls Logo

Honeywell CENTRA LINE LION CLLIONLC01 - Page 39

Honeywell CENTRA LINE LION CLLIONLC01
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LION System Description of the CLLIONLC01
39 EN1Z-0921GE51 R0709
C-Bus Termination Switch S1
The CLLIONLC01 features a 3-position C-Bus termination
switch S1.
This switch must be set in accordance with the given C-Bus
configuration.
al l
end
S1
C-Bus
mi d
9.6k
76k
76k
Fig. 57 C-Bus termination switch
Switch
setting S1
Baud rate
9.6k all
Up to 9600 baud (default setting)
76k mid Up to 76800 baud without bus termination
76k end
Up to 76800 baud with bus termination
controller at the end of the C-Bus
Table 40 CLLIONLC01 C-Bus termination switch S1
settings
Memory
Memory Size Usage
SRAM 512 KB
For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Flash 2 MB
Firmware (1 MB) and
application (1 MB) storage
EPROM 128 KB For bootstrap loader
Table 41 CLLIONLC01 memory
Note
The CLLIONLC01 does not contain a battery. RAM (data
and realtime clocktime) is buffered for 3 days by a super
capacitor.

Table of Contents