LION System Description of the I/O Modules
41 EN1Z-0921GE51 R0709
Terminals
25 26
74
78
73 77
72 76
71
75
24
V~
24
V~
24
V~0
24
V~0
COM
B
COM
B
COM
A
COM
A
AI8
8
AI7
7
AI6
6
AI5
5
AI4
4
AI3
3
AI2
2
AI1
1
18171615141312
GND
11
GND GND GND GND GND GND GND
22
V
21
10
GND
9
GND
AUX
V
AUX
Fig. 59 Terminal assignment and internal connections of
analog input modules
Ter-
minal
SIGNAL Comment
71, 75 COM a
2-wire communication bus
(LON/Panel Bus)
72, 76 COM b
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
1…8 AI1 … AI8 Analog inputs 1…8
9…18 GND
Ground. All grounds are connected
internally to each other
21, 22
10 VDC/
5 mA, ±2 %
Auxiliary voltage signal (used e.g. for
supplying setpoint potentiometers)
25, 26
Shield connection (functional earth),
internally connected to the DIN rail
Table 43 Description of analog input module terminals
Notes
Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a L
ONWORKS shield, since
L
ONWORKS requires a resistor and a capacitor.
If additional shield terminals are needed, the
XS814 Auxiliary Terminal Package can be installed.
Technical Data
Input
0(2) ... 10 VDC
0(4) ... 20 mA
(via external 499 /0.25 % resistor
NTC20k (-50…+150 °C; default)
PT1000-1 (-50…+150 °C)
PT1000-2 (0…+400 °C)
PT3000 (-50…+150 °C)
BALCO500 (-30…+120 °C)
Slow binary input
Protection Protected against failure voltage (24 VAC,
40 VDC)
Resolution
16-bit resolution
Accuracy
±75 mV (0 ... 10 V), without sensor
Table 44 Analog input modules data
Range
PT1000-1
PT1000-2
Balco500
(1
PT3000
NTC20k
(default)
NTC10k
(2
NI1000TK5000
(3
-50...-20 °C
(-58...-4 °F)
1.2 K 1.2 K 1.2 K 5.0 K 5.0 K 1.2 K
-20…0 °C
(-4…+32 °F)
0.7 K 0.7 K 0.7 K 1.0 K 1.0 K 0.7 K
0...30 °C
(32…86 °F)
0.5 K 0.5 K 0.5 K 0.5 K 0.3 K 0.5 K 0.5 K
30...70 °C
(86...158 °F)
0.7 K 0.7 K 0.7 K 0.7 K 0.5 K 0.5 K 0.7 K
70...100 °C
(158...212 °F)
1.2 K 1.2 K 1.2 K 1.2 K 1.0 K 1.0 K 1.2 K
100...130 °C
(212...266 °F)
1.2 K 1.2 K 1.2 K 1.2 K 3.0 K 1.2 K
130...150 °C
(266...302 °F)
1.2 K 1.2 K 1.2 K 5.5 K
150…400 °C
(302…752
°F)
1.2 K
(1
Balco specified for -30 °C … +120 °C, only
(2
NTC10k specified for -30 °C … +100 °C, only
(3
NI1000TK5000 specified for -30 °C … +130 °C, only
Table 45 Accuracy of analog input sensors
Note
The accuracy of the sensor itself is not included in this table.