LION System Description of the I/O Modules
59 EN1Z-0921GE51 R0709
Terminals
Actuator 2 Actuator 3
31 41 51 61
32
42
52 62
33 43 53 63
34 44 54 64
NO
NC
COM
CON
NO
NC
COM
CON
11
12
13
14
21
22
23
24
25
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
74
78
73 77
72 76
71 75
24
V~
24
V~
24
V~ 0
24
V~0
COM
B
COM
B
COM
A
COM
A
Cross connector (can be removed, as desired)
Actuator 1
Fig. 81 Terminal assignment and internal connections of
floating output module
Ter-
minal
Signal Comment
71, 75
COM a
2-wire communication bus (LON/Panel Bus)
72, 76
COM b
2-wire communication bus (LON/Panel Bus)
73, 77
24 V~
Power supply
74, 78
24 V~0
Power supply
11
REL1 N.O.
Floating relay 1 N.O. contact
12
REL1 N.C.
Floating relay 1 N.C. contact
13
R1 COM
Floating relay 1 common contact
14
R1 COM
For connection of floating relay 1 common
via cross connector*
21
REL2 N.O.
Floating relay 2 N.O. contact
22
REL2 N.C.
Floating relay 2 N.C. contact
23
R2 COM
Floating relay 2 common contact
ACTUATOR 1
24
R2 COM
For connection of floating relay 2 common
via cross connector*
31
REL3 N.O.
Floating relay 3 N.O. contact
32
REL3 N.C.
Floating relay 3 N.C. contact
33
R3 COM
Floating relay 3 common contact
34
R3 COM
For connection of floating relay 3 common
via cross connector*
41
REL4 N.O.
Floating relay 4 N.O. contact
42
REL4 N.C.
Floating relay 4 N.C. contact
43
R4 COM
Floating relay 4 common contact
ACTUATOR 2
44
R4 COM
For connection of floating relay 4 common
via cross connector*
51
REL5 N.O.
Floating relay 5 N.O. contact
52
REL5 N.C.
Floating relay 5 N.C. contact
53
R5 COM
Floating relay 5 common contact
54
R5 COM
For connection of floating relay 5 common
via cross connector*
61
REL6 N.O.
Floating relay 6 N.O. contact
62
REL6 N.C.
Floating relay 6 N.C. contact
63
R6 COM
Floating relay 6 common contact
ACTUATOR 3
64
R6 COM
For connection of floating relay 6 common
via cross connector*
25
Shield connection (functional earth),
internally connected to the DIN rail
* Do not connect by wire!
Table 58 Description of floating output module terminals
Status LED Behavior
The respective pair of status LEDs will display the following:
Actuator 1
Mode LED
Closing Opening
Not
moving
Green LED ON OFF OFF
Auto
Red LED OFF ON OFF
Green LED Flashing OFF Flashing
Override
Red LED OFF Flashing Flashing
Table 59 LED behavior (for e.g., floating output 1)
Status LEDs with Manual Overrides
1
2
3
UTO
0
!
100
Fig. 82 Manual overrides (rotary knobs)
The floating output module is equipped with manual
overrides: one for each floating output. These rotary knobs
can be manually set to either "AUTO" or "0 … 100%"
(infinitely adjustable).
NOTICE
Damage to the electronic module!
► Do not use a tool to adjust the rotary knobs.
► Do not use excessive force. Adjust only by hand.
Manual Override in the AUTO Position
When a manual override of the CLIOPR825A is set to
AUTO, the following applies:
• The output signal of the respective floating output (R1 +
R2 or R3 + R4 or R5 + R6) will be as commanded.
• The respective pair of status LEDs will be ON/OFF as
commanded.
Manual Override in the Override Position (0…100%)
When a manual override of the CLIOPR825A is set to
0…100%, the respective floating output will drive to the set
position. The runtime depends upon the actuator runtime
configured using the engineering tool and on the actual
position.