Wiring and Setting Up the System LION System
EN1Z-0921GE51 R0315
24
Connecting Single Bus Controller Systems
This section describes how to connect a controller system
which uses Panel Bus I/O modules only or L
ONWORKS
Bus I/O modules only.
Controller and I/O Modules on a Single Rail
Connect controller and I/O modules using the bridge
connectors.
This provides power supply and communication connection.
No further wiring is necessary.
Controller and I/O Modules on Several Rails in a
Single Cabinet
The rails of a controller system are connected in series.
Connect the rail ends as follows:
Power supply
via power supply terminals 73, 74 or 77, 78
Communication
via communication terminals 71, 72 or 75, 76
I/O
I/OI/O
I/O
I/O
I/O
I/O
I/O
I/O
75
75
71
71
71
71
76
76
72
72
72
72
77
77
73
73
73
73
78
78
74
74
74
74
CPU
1 2
Fig. 32 Wiring the power supply and the communication
lines to the I/O modules
Max. Power Cable Length
The max. length for power supply cable per side is 3 m. This
includes the connection cables between the rails, the
lengths of the modules, and the cable from the transformer.
Panel Bus I/O Modules in Separate Rooms
In this scenario, communication and reference voltage
(24 V0) must be connected between the rooms.
Connect the last module of room 1 to the first module of
room 2:
Reference voltage
via power supply terminals 74 or 78
terminals 73 and 77 must not be connected
Communication
via communication terminals 71, 72 or 75, 76
PANEL
I/O
PANEL
I/O
PANEL
I/O
75
75
71
76
76
72
77
7773
78
78
74
MAX. 40 m
24 V0
CPU
1 2
Fig. 33 Wiring the Panel Bus I/O modules in separate
rooms
Max. Cable Length
The max. cable length for connecting room 1 and room 2 is
40 m.