LION System Wiring and Setting Up the System
27 EN1Z-0921GE51 R0315
Setting Address of Panel Bus I/O Modules
During engineering, each Panel Bus I/O module is assigned
its own unique address. For the sake of clarity for
maintenance personnel, it is recommended that you
address the Panel Bus I/O modules in ascending order
0 through F.
Hex switch 0 1 2 3 4 5 6 7
Address 01 02 03 04 05 06 07 08
Hex switch 8 9 A B C D E F
Address 09 10 11 12 13 14 15 16
Table 24 HEX switch settings and addresses
Use the rotary HEX switch to set the address to the one
already defined using the engineering tool.
LOCK
4
4
Fig. 37 HEX switch location
NOTE:
If the HEX switch is changed, the Panel Bus I/O
module will revert to its default configuration.
NOTE: With LONWORKS Bus I/O modules, the HEX
switch is without function.
Setting I/O Bus Switch
Set the I/O Bus switch S2 of the CLLIONLC01 depending
on the modules connected to terminals 71 … 78 and the
desired communication as follows:
Communication S2 setting Terminals
LONWORKS Bus
only
LON 71 … 74 L
ONWORKS Bus
75 … 78
LONWORKS Bus
11 … 14
LONWORKS Bus
Panel Bus and
L
ONWORKS Bus
Panel 71 … 74 Panel Bus
75 … 78 Panel Bus
11 … 14 L
ONWORKS Bus
Table 25 I/O Bus switch settings
Panel
LO N
S2
I/O Bus
Fig. 38 S2 I/O Bus switch