LION System Wiring and Setting Up the System
27 EN1Z-0921GE51 R0315
Setting Address of Panel Bus I/O Modules
During engineering, each Panel Bus I/O module is assigned
its own unique address. For the sake of clarity for
maintenance personnel, it is recommended that you
address the Panel Bus I/O modules in ascending order
0 through F.
Hex switch 0 1 2 3 4 5 6 7
Address 01 02 03 04 05 06 07 08
Hex switch 8 9 A B C D E F
Address 09 10 11 12 13 14 15 16
Table 24 HEX switch settings and addresses
► Use the rotary HEX switch to set the address to the one
already defined using the engineering tool.
LOCK
4
4
Fig. 37 HEX switch location
NOTE:
If the HEX switch is changed, the Panel Bus I/O
module will revert to its default configuration.
NOTE: With LONWORKS Bus I/O modules, the HEX
switch is without function.
Setting I/O Bus Switch
► Set the I/O Bus switch S2 of the CLLIONLC01 depending
on the modules connected to terminals 71 … 78 and the
desired communication as follows:
Communication S2 setting Terminals
LONWORKS Bus
only
LON 71 … 74 L
ONWORKS Bus
75 … 78
LONWORKS Bus
11 … 14
LONWORKS Bus
Panel Bus and
L
ONWORKS Bus
Panel 71 … 74 Panel Bus
75 … 78 Panel Bus
11 … 14 L
ONWORKS Bus
Table 25 I/O Bus switch settings
Panel
LO N
S2
I/O Bus
Fig. 38 S2 I/O Bus switch