LION System Description of the CLLIONLC01
33 EN1Z-0921GE51 R0315
CLLIONLC01 Terminals
71
11
8
5
1
75
72
12
9 6
2
76
73
13 10 7
3
77
74
14
4
78
COM
A
LON
1
C+ C+
C- C-
SHIELD SHIELD
LON
2
LON
2
LON
1
COM
A
COM
B
COM
B
24
V~
24
~
24
~
24
V~0
24
~0
24
~0
NO
24
~0
8765
4
3
21
WATCHDOG
RELAY
Fig. 46 Terminal assignment and internal connections of
the CLLIONLC01
Ter-
minal
Signal Comment
71, 75 COM a
2-wire communication bus
(LON/Panel Bus)
72, 76 COM b
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NO Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Table 28 Description of CLLIONLC01 terminals
Features
LONWORKS Interface and Terminals
The CLLIONLC01 Controller Module features
An RJ45 socket serving as an interface to connect
laptops to the L
ONWORKS Bus
LONWORKS terminals 11, 12, 13, and 14 to connect
L
ONWORKS Bus I/O modules or other LONWORKS devices
to the CLLIONLC01 Controller or other L
ONWORKS
controllers.
687 354 21
11
12
13
14
LON
Fig. 47 LONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Pin Signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 … 8 Not used
Table 29 Signals of LONWORKS interface
LONWORKS Service LED and Button
The CLLIONLC01 is equipped with a LONWORKS service
button and corresponding L
ONWORKS Service LED (status:
yellow/OFF).
Fig. 48 LONWORKS service button (1) and service LED (2)
See also section "Troubleshooting" on page 39.