LION System System Overview
5 EN1Z-0921GE51 R0315
I/O Module Overview
Panel Bus
module
LONWORKS
Bus module
Description Inputs Outputs Manual controls LEDs
1)
CLIOP821A CLIOL821A Analog input module 8
CLIOP822A CLIOL822A Analog output module 8 8 status LEDs
CLIOPR822A CLIOLR822A Analog output module 8 8 Manual overrides 8 status LEDs
CLIOP823A CLIOL823A Binary input module 12 12 status LEDs
CLIOP824A CLIOL824A Relay output module 6
2)
6 status LEDs
CLIOPR824A CLIOLR824A Relay output module 6
2)
6 Manual overrides 6 status LEDs
CLIOPR825A Floating output module 3 3 Manual overrides 3 pairs of status LEDs
CLIOP830A -- Mixed I/O module 20 14 -- 18 status LEDs
CLIOP831A -- Mixed I/O module 20 14 -- 18 status LEDs
1
)
In addition to the power LED and service LED
2)
Changeover outputs
Table 3 Overview of I/O modules
Manual Overrides as per EN ISO 16484-2:2004
The manual override switches and potentiometers of the output modules (…R822A, …R824A, and CLIOPR825A) support direct
operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the
LION Controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the cor-
responding output LED will blink continuously, and the output module will send a feedback signal with the status "manual
override" and the given override position to the LION Controller (which will then also store this information in its alarm memory).
NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Corresponding Terminal Sockets
I/O module
CLIOP/CLIOL…
Socket Scope of delivery
…821
XS821-22
XSU821-22
1 terminal socket,
1 bridge connector
1 swivel label holder
…822
…823
XS823
XSU823
1 terminal socket,
1 bridge connector
1 swivel label holder
…824
XS824-25
XSU824-25
1 terminal socket,
1 bridge connector
1 swivel label holder
1 cross connector
…825
Table 4 Pluggable I/O modules and corresponding
terminal sockets
NOTE: In the following, e.g., …822 is used to summarize
all analog output modules (Panel Bus/L
ONWORKS
Bus, with/without manual overrides).