CIPer
TM
MODEL 30 EXPANSION IO MODULES - INSTALLATION INSTRUCTIONS
31-00319-02
8
Terminal Description
WEB-O3022H
Terminal
Description
1, 3
Universal inputs UI-1 & UI-2
2
COM terminal for UI-1 & UI-2
4
Universal inputs UI-3
5
COM terminal for UI-3
6
Supplies 20V DC
7
24V AC output from controller for DO devices
8
HOT (B) terminal. Supplies power to common side of controller’s DO-2
9
HOT (A) terminal. Supplies power to common side of controller’s DO-1
10
DO-1(A)
11
GND terminal for DO-1(A) & DO-2(B)
12
DO-2(B)
13, 15
Universal inputs UI-4/AO-1 & UI-5/AO-2
14
COM terminal for UI-4/AO-1 & UI-5/AO-2

Other manuals for Honeywell CIPer 30