Electrical Installation - Field and Host Port Connections
Part No.: 4417590_Rev13 CIU 888
Installation Manual 3 - 7
$*6
Connections over short distances can be made with a “null modem”
cable. If the distance is longer than 15 m (50 ft), a modem connection
must be used. The connection to the modem depends on the type of
modem used.
FIGURE 3-6 Field RS232C Port Connection Details
3.4.3.2 Field RS232-485 Port in RS485 mode
Refer to FIGURE 3-7 for RS-485 pin configurations and connections.
Cable requirements for RS-485 connection:
Max. length: 1000 m (3000 ft)
Minimum one twisted pair (typical: 50 twists per metre) with a
ground wire
Overall shielded
Rmax:0.12
/m (per line)
Cmax:119 pF/m
Lmax:1.45 mH/m
Refer FIGURE 3-7 (A) for full duplex RS-485 connection or FIGURE 3-7
(B) when a half duplex RS-485 connection is required. For half-duplex
connect signals RXA with TXA and RXB with TXB inside the cable
connectors. Place 120
resistors at the receive terminals in the cable
connectors.